beautypg.com

10 field control wiring – AERCO BMK 1500-2000 User Manual

Page 26

background image

Benchmark 1500 - 2000 Boilers

CHAPTER 2 – INSTALLATION

Page 26 of 188

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0097_0D

Ph.: 800-526-0288

GF-142

2.10 FIELD CONTROL WIRING

Each unit is fully wired from the factory with an internal operating control system. No field control
wiring is required for normal operation. However, the C-More Control system used with all
Benchmark units does allow for some additional control and monitoring features. Wiring
connections for these features are made on the Input/Output (I/O) board located behind the
removable front panel assembly of the unit. The I/O board is located in the upper-left portion on
the front of the unit as shown in Figure 2-11. The I/O board terminal strip connections are shown
in Figure 2-12. All field wiring is installed from the rear of the panel by routing the wires through
one of the four bushings provided on the sides of the I/O board.

Refer to the wiring diagram provided below the I/O Box (Figure 2-12) when making all wiring
connections.

Figure 2-11: Input/Output (I/O) Box Location

NOTE

Use Figure 2-12 to determine the functions of the I/O PCB
connections. Do not use the silkscreened labels on the PCB itself,
as these may not match the function names.

There is a diagram of the connection functions on the cover of the
I/O Box as well.

DO NOT make any connections to the I/O Box terminals labeled
“NOT USED”. Attempting to do so may cause equipment damage.

CAUTION

I/O PCB

BOARD

TERMINAL STRIPS