Benchmark 1500 - 2000 Boilers

CHAPTER 3 – OPERATION

OMM-0097_0D

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 35 of 188

GF-142

Ph.: 800-526-0288

Table 3-1: Operating Controls, Indicators and Displays

ITEM

NO.

CONTROL,

INDICATOR OR

DISPLAY

FUNCTION

1

LED Status Indicators

Four Status LEDs indicate the current operating status as follows:

COMM

Lights when RS-232 communication is occurring

MANUAL

Lights when the valve position (fire rate) is being controlled using
the front panel keypad. This mode of operation is for service
technician use only.

REMOTE

Lights when the unit is being controlled by an external signal from
an Energy Management System

DEMAND

Lights when there is a demand for heat.

2

OUTLET
TEMPERATURE

Display

3–Digit, 7–Segment LED display continuously displays the outlet
water temperature. The °F or °C LED next to the display lights to
indicate whether the displayed temperature is in degrees
Fahrenheit or degrees Celsius. The °F or °C blinks when operating
in the Deadband Mode.

On a BST Master, display flashes & shows header temperature.

3

VFD Display

Vacuum Fluorescent Display (VFD) consists of 2 lines each
capable of displaying up to 16 alphanumeric characters. The
information displayed includes:
• Startup Messages
• Fault Messages
• Operating Status Messages
• Menu Selection
• BST Messages

4

RS-232 Port

Port permits a Laptop Computer or External Modem to be
connected to the unit’s Control Panel. AERCO offers for purchase
the RS232 Adaptor Cable (P/N 124675), which is designed to
work with this port. This cable features a DB9 connector for
connection to older computers with serial ports or can be used
with a Serial-to-USB adaptor for use in modern computer USB
ports.

5

FAULT Indicator

Red FAULT LED indicator lights when a boiler alarm condition
occurs. An alarm message will appear in the VFD.

6

CLEAR Key

Turns off the FAULT indicator and clears the alarm message if the
alarm is no longer valid. Lockout type alarms will be latched and
cannot be cleared by simply pressing this key. Troubleshooting
may be required to clear these types of alarms.

7

READY Indicator

Lights ON/OFF switch is set to ON and all Pre-Purge conditions
have been satisfied.

8

ON/OFF Switch

Enables and disables boiler operation.

9

LOW WATER LEVEL

TEST/RESET Switches

Allows operator to test operation of the water level monitor.

Pressing TEST opens the water level probe circuit and simulates a
Low Water Level alarm.

Pressing RESET resets the water level monitor circuit.

Pressing the CLEAR key (item 6) resets the display.