KEYENCE DL-RS1A User Manual

Page 13

background image

11

Parameters of Commands and Responses

For information on each error, refer to "SK-1000 Series Instruction Manual"

When the data read from a sensor amplifier is "00005":

"5" converted to binary number is "0000 0000 0000 0101".

Therefore, this data indicates that an "Overcurrent error" and a "Head error" have
simultaneously occurred at the sensor amplifier from which the data was read.

If no error has occurred at the sensor amplifier, the data "00000" is returned.


*4

You can read data number "036" to check the judgment output status.
Convert the two digit number (ASCII characters) read from the sensor amplifiers to a binary
number and check the ON/OFF state of each bit to check the judgment output status.

When the data read from a sensor amplifier is "05":

"05" converted to binary number is "0101".

During N.O.

*5

When the data read from the sensor amplifiers is one of the following values, it is not a
comparator value but has a specific meaning.

*6

This is -999.8 when the temperature is not acquired correctly.

*7

This is 999.8 when the humidity is not acquired correctly.

*8

If a prohibited combination of functions is written, an "abnormal setting (1)" will result.
For details on each function, see the "SK-1000 Series Instruction Manual."

9

Unused

10

Unused

11

Amplifier communication error

12

Unused

13

Unused

Bit

Judgment output

N.O.

N.C

0

0: HI Judgment output OFF,

1: HI judgment output ON

0: HI Judgment output ON,

1: HI judgment output OFF

1

0: LO Judgment output OFF,

1: LO Judgment output ON

0: LO Judgment output ON,

1: LO Judgment output OFF

2

0: GO Judgment output OFF,

1: GO Judgment output ON

0: GO Judgment output ON,

1: GO Judgment output OFF

3

0: Alarm output ON,

1: Alarm output OFF

0: Alarm output ON,

1: Alarm output OFF

Readout data

Details

+EE.EEE

The sensor amplifier encountered an error.

+99.999

The value is +99.999 or exceeds the upper display range.

-99.999

The value is -99.998, -99.999, or exceeds the lower display range.

-99.998

The value is "-----".

Bit

Sensor amplifier error details

Reference

Bit 0: Overcurrent error

Bit 2: Head error

Reference

Bit 3: Alarm output ON

Bit 0: HI judgment output ON

Bit 2: GO judgment output ON

Bit 1: LO judgment output OFF

Parameters of Commands and Responses

*9

The execution result for the item last requested, either the zero shift execution request or zero
shift reset execution request, is read.

*10 This item includes the results for the initial reset execution.
*11 You can read data number "56" to check the system parameter of the sensor amplifier. The

system parameter means the polarity of judgment output and alarm output, and the setting for
analog output. Convert the two digit number (ASCII characters) read from the sensor amplifiers
to a binary number and check the ON/OFF state of each bit to check the system parameter.

When the data read from a sensor amplifier is "006":

"6" converted to binary number is "0110".

Therefore, the setting of the amplifier from which the data is read is "NPN output" and
"Analog output 1 to 5 V".

*12 The external input status is where the external input is [1] when input status is ON, [0] when

status is OFF, and the 0,1,2,3 bits correlate with external input 1,2,3,4.

When the data read from a sensor amplifier is "06":

"6" converted to binary number is "0110".

Bit

Initial setting details

0

0: NPN output, 1: PNP output

3, 2, 1

000: Analog output OFF

001: 0 to 5 V

010: -5 to +5 V

011: 1 to 5 V

100: 4 to 20 mA

Reference

Bit 3, 2, 1: 1 to 5 V

Bit 0: NPN output

Reference

External input 1: OFF

External input 4: OFF

External input 2: ON

External input 3: ON