Commands and Responses

„ Read with external input to the DRQ terminal (DRQ read)

You can send an input signal (by short-circuiting DRQ (terminal number 6) and SG (terminal number
1, 4, or 5)) from an external device such as a PLC instead of sending a command.

Response

Error response

*1

The data length is different depending on the data being read. (Up to 10 characters)

*2

SK-1000: ±**.*** (reading range is -99.999 to +99.999)

*3

Data length: 2 characters
On the SK-1000 Series, the judgment output (HI/LO/GO output) and the alarm output ON/OFF
are displayed with 2-digit number (ASCII characters). Convert the 2-digit number (ASCII
characters) read to a binary number and check the ON/OF status of each bit to check the
judgment output status.

When the read data is "05":
"05" is converted to the binary number "0101".
When N.O.

Bit

Judgment output

When N.O.

When N.C.

0

0: HI judgment output OFF,

1: HI judgment output ON

0: HI judgment output ON,

1: HI judgment output OFF

1

0: LO judgment output OFF,

1: LO judgment output ON

0: LO judgment output ON,

1: LO judgment output OFF

2

0: GO judgment output OFF,

1: GO judgment output ON

0: GO judgment output ON,

1: GO judgment output OFF

3

0: Alarm output ON,

1: Alarm output OFF

0: Alarm output ON,

1: Alarm output OFF

2 ms min.

Input signal

ON

OFF

SG

RD

SD

SG

SG

DRQ

D

R

CR LF

Data of the sensor
amplifier with ID:00*

2

,

,

,

,

Data of the sensor
amplifier with ID:01*

2

Data of the sensor
amplifier with the last ID No.*

2

,

,

Sensor amplifier with ID:00

Sensor amplifier with ID:01

Sensor amplifier with the last ID No.

Control
output*

3

Control
output*

3

Control
output*

3

E

R

CR LF

,

D

R

,

Error No.

Reference

Bit 3: Alarm output ON

Bit 0: HI judgment output ON

Bit 2: GO judgment output ON

Bit 1: LO judgment output OFF

Commands and Responses

Writing

External devices such as PLC's use the following communication commands to write data to
DL-RS1A.

Attempting to write data with "read-only" attribute results in a communication error and an
error response (error number: 22).

„ Write to the specified sensor amplifier (SW command)

Command

Response

Error response

„ Write to all sensor amplifiers (AW command)

Command

Response

Error response

Point

S

W

CR LF

ID No.

Data No.

,

,

Setting data*

,

S

W

CR LF

ID No.

Data No.

,

,

E

R

CR LF

,

S

W

,

Error No.

A

W

CR LF

Data No.

,

Setting data*

,

A

W

CR LF

Data No.

,

E

R

CR LF

,

A

W

,

Error No.