Disable the Zero Shift Function
Press and hold the [PRESET] button to disable the zero shift function.
Output Switch
Either light-ON (L-on) mode or dark-ON (D-on) mode can be selected.
1
While the current value is displayed,
press the [MODE] button once.
2
Use
to switch the output (
/
), then press the [MODE] button again.
The output change completes, and the display returns to the current value.
Display when the LV-S31 is Connected
When the LV-S31 is connected, the workpiece position is numerically displayed on the main
screen (red display) using the center position as [5000].
The display changes as follows according to the workpiece position.
Initializing the Settings
Initialization Method
1
Press and hold the [SET] and
[PRESET] buttons simultaneously
for more than three seconds.
2
Use the
to select "
", then press the [MODE] button.
3
Use the
to select "
", then press the [MODE] button.
After initialization is complete, the display returns to the current value.
Initial Settings
Key Lock
The key lock function disables button operation to prevent unauthorized use.
Activating Key Lock
1
Press and hold the [MODE] button
and
(or
) simultaneously for
three seconds or more.
2
The screen displays "
", disabling
key operation.
Deactivating Key Lock
1
Press and hold the [MODE] button
and
(or
) simultaneously for
three seconds or more.
2
The screen displays "
", enabling
key operation.
Error Displays and Corrective Actions
For errors other than the above, contact your nearest KEYENCE office.
Connecting to External Devices
Cable Type
The light intensity may not be set to "
" when the reflective model sen-
sor head is first installed.
In this case, using the zero shift function to set the state with no target
present to "
" will make it easier to see the difference in light intensi-
ties.
•
When LV-S31 is connected
(side farther from the sensor is
ON) or
(side nearer the sensor is ON) can be selected.
•
When using the 2-output type, output 1 and 2 can be set indi-
vidually.
Display
Meaning
Out of detection range
The detector is nearer to the sensor side than numerical display range
Centering on 5000, the value increases as the workpiece distance
increases from the sensor
The workpiece is farther from the sensor than the numerical display
range
Out of detection range
Setting
Initial value
Power mode
TURBO
Detection mode
Std (Normal)
Setting value
50
Output switch
L-on
Reference
Point
Near
Far
Press and hold for 3 seconds or more
Error display
Cause
Solution
Overcurrent in the control out-
put.
•
Check the load and return the cur-
rent within the rated range.
•
Check that the output wire is not
contacting any other wire or frame.
Sensor head cable is broken or
is not connected.
•
Check that the sensor head is
connected.
•
Check sensor head cable for dam-
age.
•
Check the sensor head cable con-
nector for damage or loose con-
nections.
After checking, turn the power
OFF and ON.
Internal data write / load failed.
Turn the power OFF and ON. If the
data is not recovered, initialize the
settings.
Key lock function is enabled, or
if using M8 connector types or
monitor output types, the
power mode was fixed to
MEGA mode using the selec-
tor switch.
•
Release the key lock.
•
Check that the sensor amplifier
selector switch is set to MEGA
mode.
The DTM indicator
flashes.
Correction error in DATUM1 or
DATUM 2 mode.
See "LV-N10 Series User’s Manual"
for details.
LV-N11N / N12N
LV-N11P / N12P
Input / output circuit diagram
Input / output circuit diagram
*1 LV-N11N only
*1 LV-N11P only
10-30 VDC
3.3 VDC
Black
(Control output 1)
(Control output 2)
PLC, etc.
Short-circuit current
1 mA or less
White
Pink
Brown*
1
Blue*
1
Sensor main circuit
Ov
ercurrent protection circuit
0V
Load
Load
Short-circuit current
2 mA or less
10-30 VDC
PLC, etc.
Pink
Blue*
1
0V
Black
(Control output 1)
(Control
output 2)
White
Brown*
1
Sensor main circuit
Ov
ercurrent protection circuit
Load
Load