Command word encoding, Bits 15 & 14, Bits 8-13 – Hardy HI 1746-WS User Manual
Page 37: Bits 0-7, Command word encoding -7, Bits 15 & 14 -7 bits 8-13 -7 bits 0-7 -7, Primary and remote communication

Chapter 4 - Setup
4-7
FIG. 4-2 PRIMARY AND REMOTE
COMMUNICATION DIAGRAM
Command Word
Encoding
You may write up to 7 words at a time to either the
Logical O file or the Logical M0 file. Word #0 of the
8 word output file is used to specify where words 1-7
go in either the logical O or M0 file, is called the
“Command Word”. Word #0 of the I file will always
be a copy of the “Command Word”.
Bits 15 & 14
11 = write 0 to 7 words to the logical M0 file, Read 7
words from the M1 file.
NOTE:
You need to run any command through M files before
previous writes take effect.
01 = write 0 to 7 words to the logical O file, Read
(configured) I
10 = configure 0 to 7 words for the I file return, con-
figure 7 words to read from Logical I file.
00 = the configured I file returned.
Bits 8-13
Number of words to write to the logical M0 or logical
O file.
Bits 0-7
Offset (in words) in the logical M0 or logical O file
where the write begins.
Command Word - 16 bits
Bits 15-14
Bits 13-8
Bits 7-0