Hitachi Lightning 9900™ User and Reference Guide

85

5.2.5 Input Voltage Tolerances

Table 5.3 lists the input voltage tolerances for the three-phase 9960. Transient voltage
conditions must not exceed +15-18% of nominal and must return to a steady-state tolerance
within of +6 to -8% of the normal related voltage in 0.5 seconds or less. Line-to-line
imbalance voltage must not exceed 2.5%. Nonoperating harmonic contents must not exceed
5%.

Table 5.3

Input Voltage Specifications for Three-Phase Power

Frequency

Input Voltages (AC)

Wiring

Tolerance (%)

60 Hz

± 0.5 Hz

200V, 208V, or 230V

three-phase three wire + ground +6% / -8%

50 Hz

± 0.5 Hz

200V, 220V, 230V, or 240V three-phase three wire + ground +6% / -8%

50 Hz

± 0.5 Hz

380V, 400V, or 415V

three-phase four wire + ground

+6% / -8%

Note: User input requires a 30-amp circuit breaker for three-phase power.