92 Chapter

5

Planning for Installation and Operation

5.3.5 Input Voltage Tolerances

Table 5.6 lists the input voltage tolerances for the single-phase 9900 subsystem. Transient
voltage conditions must not exceed +15-18% of nominal and must return to a steady-state
tolerance of between +6 and -8% of the normal related voltage in 0.5 seconds or less. Line-
to-line imbalance voltage must not exceed 2.5%. Nonoperating harmonic contents must not
exceed 5%.

Table 5.6

Input Voltage Specifications for Single-Phase Power

Frequency

Input Voltages (AC)

Wiring

Tolerance(%)

60 Hz

±0.5 Hz 200V, 208V or 230V

Single-phase two wire + ground +6% or -8%

50 Hz

±0.5 Hz 200V, 220V, 230V or 240V Single-phase two wire + ground +6% or -8%

Note: User input requires a 20-amp circuit breaker for single-phase power.