Hitachi Lightning 9900™ User and Reference Guide

97

Floor cutout area for cables

Caster

Screw jack

Service clearance

G

Grid panel (over 450mm

× 450mm)

Opening on the bottom of the frame
(for external cable entry)

(Unit : mm)

800

250

*2

250

*2

2400

680

60

60

118

118

564

Front

175

*2

175

*2

86

86

578

16

16

718

166

166

418

750

800

800

G

G

280

598

76

76

100

254

Recommended value: 400

( 300 - 570 ) *1

Recommended value: 300

( 250 - 400 ) *1

*1: Values in parentheses show allowable range of the floor cutout dimension. The floor cutout should be planned in the center

of the DKC. In case that the floor cutout is planned in a right position for the external cable work and it is within the allowable

range, the cutout position may be off-center. In this case, check the relation between the positions of the cutout and the opening

on the bottom of the frame. If the floor cutout width is planned more than 520 mm, be careful about the restriction of the movable

direction because there is a possibility that the caster wheels fall down into the cutout.
*2: These dimensions vary with the floor cutout dimension.

Figure 5.14 9960 Controller Frame Service Clearance and Cutouts (millimeters)