beautypg.com

Technical data – Beckett RWF40 Manual User Manual

Page 55

background image

HVAC Products

CC1B7865en

01.09.2005

55/57

11. Technical data


Resolution: > 15 bit

Measuring accuracy

Ambient temperature error

Resistance thermometer:

≤ 0.05 %

≤ 50 ppm / K

Thermocouples:
≤ 0.25 %

≤ 100 ppm / K

Standard signals:

≤ 0.1 %

≤ 100 ppm / K


Values include linearization tolerances.


Transducer Probe

break Short-circuit

Resistance thermometer

X

X

Thermocouples X

-

DC 0…10 V

-

-

DC 0…20 mA

-

-

DC 4…20 mA

X

X


- = is

not detected

X = is detected, and «–1999» appears on the display

Ö

Chapter 10 «What to do if...»



Permissible ambient temperature range:
-20…+50 °C

Permissible storage temperature range:
-40…+70 °C

Climatic conditions:
Relative humidity

≤ 95 % (noncondensing)

Degree of protection to EN 60529:
Front IP 65
Rear IP 20

Electromagnetic compatibility (EMC):
To NAMUR recommendation NE 21, EN 50 081 part 1, EN 50 082 part 2

11.3.1 Measuring accuracy

11.3.2 Monitoring of measuring circuit

11.3.3 Environmental conditions