HVAC Products

CC1B7865en

01.09.2005

21/57

5. Operating modes

C111: XX1X ... XX3X

Outside sensor

Heating curve slope H

Setting: 0.0 ... 4.0

C112: XX0X

SP1 via buttons

C112: XX1X

SP1 via outside sensor

C111: XXX2

Section 5.4.4 "Exter-
nal setpoint, binary
setpoint shift"

C111: XXX1

Setpoint changeover

C111: XXX0

No function

Setpoint SP2

SP2 via buttons

C111: X6XX ... XAXX

Analog setpoint shift

SPL / oLLo

SPH / oLHi

C111 and C112 are
described in chapter 8

Weather-dependent
setpoint shift:

No

Yes

D2 open

D2 closed

+

Active setpoint

Setpoints SP1 and SP2 are
entered on the user level.
Section 6.2 "User level"

Connection of binary input D2
Section 4.2 "Assignment of terminals"

7865f05e/1202

1)

1)


¹) Only with RWF40.0X2B97

5.4.1 Setpoint changeover «SP1 / SP2», analog setpoint shift