HVAC Products

CC1B7865en

01.09.2005

49/57

9. Self-setting function

Start

t

w

x

7865d13/1099


The controlled system data recorded for the forced oscillations are used to calculate the
controller parameters «rt, dt, Pb.1» and a filter time constant for actual value filtering
that is optimized for this controlled system.

− High-fire operation in the «modulating burner» mode
− The thermostat function (relay 1) must be constantly activated, otherwise «tunE» will

be canceled and no optimized controller parameters will be adapted

− The above mentioned actual value oscillations during self-setting must not exceed the

upper threshold of the thermostat function (increase if necessary, and lower the
setpoint)


Conditions