C111, Configuration – Beckett RWF40 Manual User Manual
Page 38

38/57 CC1B7865en
01.09.2005
HVAC
Products
8. Configuration
0000
C111
7865p03/0200
Analog input 1
Pt100, 3-wire, IEC 751
0
Pt100, 2-wire, IEC 751
1
Ni100, 3-wire, DIN 43760
2
Ni100, 2-wire, DIN 43760
3
Pt1000, 3-wire, IEC 751
4
Pt1000, 2-wire, IEC 751
5
Ni1000, 3-wire, DIN 43760
6
Ni1000, 2-wire, DIN 43760
7
LG-Ni1000, 3-wire
8
LG-Ni1000, 2-wire
9
NiCr-Ni / K
A
Cu-CuNi / T
b
NiCroSil-NiSil / N
C
Fe-CuNi / J
d
Standard signal DC 0…20 mA
E
Standard signal DC 4…20 mA
F
Standard signal DC 0…10 V
G
Standard signal DC 0…1 V
H
Pt-RhPt / S ¹)
i
Pt-RhPt / R ¹)
j
Pt-RhPt / B ¹)
L
Analog input 2
No function
0
External setpoint, 1 k
Ω resistance potentiometer
1
External setpoint, DC 0…20 mA
2
External setpoint, DC 4…20 mA
3
External setpoint, DC 0…10 V
4
External setpoint, DC 0…1 V
5
Analog setpoint shift, 1 k
Ω resistance potentiometer
6
Analog setpoint shift, DC 0…20 mA
7
Analog setpoint shift, DC 4…20 mA
8
Analog setpoint shift, DC 0…10 V
9
Analog setpoint shift, DC 0…1 V
A
Position feedback resistance potentiometer 1 k
Ω ¹)
b
Position feedback 0...20 mA ¹)
C
Position feedback 4...20 mA ¹)
d
Position feedback 0...10 V ¹)
E
Position feedback 0...1 V ¹)
F
¹) Only with RWF40.0X2B97
8.1 C111 inputs