C113, Configuration – Beckett RWF40 Manual User Manual

Page 44

background image

44/57 CC1B7865en

01.09.2005

HVAC

Products

8. Configuration

*

The setting of the decimal place has an impact
on the parameters that are dependent on the
actual value!

0000

C113

7865p05/0200

Unit address

Address 0

0

0

Address 1

0 1

...

...

Address 99

9 9

Decimal place, unit, Baud rate

No decimal place, degrees Celsius, 9600 Bd

0

One decimal place, degrees Celsius, 9600 Bd

1

No decimal place, degrees Fahrenheit, 9600 Bd

2

One decimal place, degrees Fahrenheit, 9600 Bd

3

No decimal place, degrees Celsius, 19200 Bd ¹)

4

One decimal place, degrees Celsius, 19200 Bd ¹)

5

No decimal place, degrees Fahrenheit, 19200 Bd ¹)

6

One decimal place, degrees Fahrenheit, 19200 Bd ¹)

7

No decimal place, degrees Celsius, 4800 Bd ¹)

8

One decimal place, degrees Celsius, 4800 Bd ¹)

9

No decimal place, degrees Fahrenheit, 4800 Bd ¹)

A

One decimal place, degrees Fahrenheit, 4800 Bd ¹)

b

Signal for out-of-range

Limit comparators OFF

0

Limit comparators ON

1


Factory setting

0

1

1

0


¹) Only with RWF40.0X2B97

8.3 C113 instrument address, dimensional unit, out-of-range

*