Parameter settings, Hyst, Pb.1 – Beckett RWF40 Manual User Manual
Page 36

36/57 CC1B7865en
01.09.2005
HVAC
Products
7. Parameter settings
The parameter is shown on the lower setpoint display (green) and the parameter value
on the upper / actual value display (red).
Parameter Display
Value
range
Factory
setting
Remarks
Limit value for limit
comparator
1)
AL
-1999...+9999 digit
0
AL
HYSt
w
Measured value
7865d10e/0300
Output 4
Ö
Section 8.2 «
C112 – limit
comparator, controller type, setpoint
«SP1», «locking»
Switching differential
for limit comparator
1)
HYSt
0...999.9 digit
1
Switching differential at the edges for
the limit comparators
Ö
Section 8.2 «
C112 – limit
comparator, controller type, setpoint
«SP1», «locking»
Proportional band
1)
Pb.1
0.1...999.9 digit
10
Affects the P-response of the controller
Derivative time
dt
0...9999 s
80
Affects the D-response of the controller.
Within dt = 0, the controller has no D-
response.
For modulating controllers, dt = rt / 4 or
0 must be entered.
Integral action time
rt
0...9999 s
350
Affects the I-response of the controller.
With rt = 0, the controller has no I-
response
Dead band (neutral
zone)
1)
db
0...999.9 digit
1
For floating output
100%
-100%
Y
X
W
db
7865d11/1099
1)
Setting of the decimal place has an impact on this parameter.
10
AL
7865p06/0200