7. Parameter settings

The parameter is shown on the lower setpoint display (green) and the parameter value
on the upper / actual value display (red).

Parameter Display

Value

range

Factory

setting

Remarks

Limit value for limit
comparator

1)

AL

-1999...+9999 digit

0

AL

HYSt

w

Measured value

7865d10e/0300

Output 4

Ö

Section 8.2 «

C112 – limit

comparator, controller type, setpoint
«SP1», «locking»

Switching differential
for limit comparator

1)

HYSt

0...999.9 digit

1

Switching differential at the edges for
the limit comparators

Ö

Section 8.2 «

C112 – limit

comparator, controller type, setpoint
«SP1», «locking»

Proportional band

1)

Pb.1

0.1...999.9 digit

10

Affects the P-response of the controller

Derivative time

dt

0...9999 s

80

Affects the D-response of the controller.
Within dt = 0, the controller has no D-
response.
For modulating controllers, dt = rt / 4 or
0 must be entered.

Integral action time

rt

0...9999 s

350

Affects the I-response of the controller.
With rt = 0, the controller has no I-
response

Dead band (neutral
zone)

1)

db

0...999.9 digit

1

For floating output

100%

-100%

Y

X

W

db

7865d11/1099

1)

Setting of the decimal place has an impact on this parameter.

10

AL

7865p06/0200