26/57 CC1B7865en

01.09.2005

HVAC

Products

5. Operating modes


Slope «H» of the heating curve can be used to adjust the setpoint in response to the
outside temperature, as shown in the diagram. The common origin of the heating curves
is set at (20 °C / 20 °C). The effective range of the weather-dependent setpoint is
restricted by the setpoint limits «

SPH» and «SPL».

Setpoint (°C)

Outside temperature (°C)

HYS1

+20

+20

0

H smaller

-10

10

SPL

SPH

H larger

HYS3

7865d01e/1102

oLHi

1)

oLlo

1)


¹) Only with RWF40.0X2B97

«HYS1» is the switch-on point for the burner, and «HYS3» is the switch-off point. As
already described, they act with the set shift relative to the weather-dependent setpoint.

Ö

Section 5.2.1 «Modulating burner, floating output»

Ö

Section 5.2.2 «Modulating burner, analog output»


5.5.1 Heating curve slope