6. Operation

٭ Press

EXIT

for 5 seconds

The LED above the hand symbol will light up.


٭

Change the position of the actuating device with

=

and

>

Relay 2 opens the actuating device as long as

=

is kept depressed.

Relay 3 closes the actuating device as long as

>

is kept depressed.

The LEDs for the actuating device indicate if «OPEN» or «CLOSE» is activated.


٭ Change the position of the actuating device with

=

and

>

The analog output delivers the position of the actuating device that was entered.

٭ Return to automatic operation by pressing

EXIT

for 5 seconds

)

When manual operation is activated, the position of the actuating device will
be set to 0 until another entry with the buttons is made.



Manual operation can only be activated if the thermostat function has set relay 1

active.

If the thermostat function sets relay 1

inactive during manual operation, manual

operation is terminated.

٭ Press

EXIT

for 5 seconds

٭ Press

=

briefly

− Relay 2 is active, relay 3 is inactive
− Analog output (optional) delivers DC 10 V

The actuating device opens.
٭ Or press

>

briefly

− Relay 2 is inactive, relay 3 is active
− Analog output (optional) delivers DC 0 V

The actuating device closes.

٭ Return to automatic operation by pressing

EXIT

for 5 seconds

)

If the thermostat function sets relay 1

inactive during manual operation,

manual operation is terminated.


6.2.2 Manual operation, modulating burner

Floating controller

Modulating controller

Thermostat mode

6.2.3 Manual operation, 2-stage burner