8. Configuration


Window function: Relay «K6» is active when the measured value lies within a window
about the setpoint (w).
Example: w = 80 °C,

AL = 5, HYSt = 2

Measured value rising: Relay «K6» switches on at 76 °C and off at 86 °C.
Measured value falling: Relay «K6» switches on at 84 °C and off at 74 °C.

AL

HYSt

w

Measured value

7865d10e/0300

Output 4


Like lk1, but inverted switching function.

AL

HYSt

w

Measured value

7865d09e/0300

Output 4



HYSt = switching differential of the window edges
AL = interval from setpoint (half the window-width)

Lower limit signaling
Function: Relay inactive when measured value < (setpoint – limit value).
Example: w = 80 °C,

AL = 10, HYSt = 2

Measured value rising: Relay «K6» switches on at 71 °C.
Measured value falling: Relay «K6» switches off at 69 °C.