PNOZ s6.1

Operating Manual PNOZ s6.1
21692-EN-08

4

– Input status, channel 2
– Switch status of the safety contacts
– Feedback loop
– Fault

}

Plug-in connection terminals (either spring-loaded terminal or screw terminal)

Safety features

The safety relay meets the following safety requirements:

}

The safety relay prevents the plant from being enabled in the following cases:

– Power supply failure
– Component failure
– Short circuit on an input circuit
– Coil defect
– Open circuit
– Earth fault

}

In each on-off cycle, the output relays on the safety device are tested to ensure they

open and close correctly

}

The unit has an electronic fuse.

Block diagram/terminal configuration

Input

Input

A1 A2

S23 S24

=

Power

Feed-

back

(Reset)

S34

S13 S14

=

Y32

(~)

K1

K2

13 23 33

24 34

14

41

42

Interface expansion

unit

( )

*

*

Centre: Front view with cover, right: Front view without cover

Grey highlighted area: Applies only with U

B

= 48 – 240 V AC/DC

*Insulation between the non-marked area and the relay contacts: Basic insulation (overvolt-
age category III), safe separation (overvoltage category II)