Ee electrical options – Detex V40 EE User Manual
Page 10
L9 = Less 9v battery
SI = Status indicator
9V Alkaline
Battery
Dis Lo Bat switch:
To disable the low-battery
indication, slide "DisLoBat"
switch to 'ON'
+RED
-BLK
OBSERVE
POLARITY
24VDC
POWER SUPPLY
RED +24V
BLACK GROUND
Status
indicator switch
1 2 3 4 5 6 7 8 9 10 1112
POWER REQUIREMENT:
.5 AMPS @ 24 VDC
+ -
EE ELECTRICAL OPTIONS
1 2
The key cylinder arming switch must be set to "OFF". To prevent the alarm
from sounding during installation, attach battery AFTER main power is applied.
Delayed Egress Device requires a connection to the Fire Alarm System.
The fire alarm connection needs to be made
Externally at the Power Supply.
During a fire alarm condition the delayed egress will be by-passed.
MAIN POWER CONNECTION: (1 & 2)
See Power Supply instructions
DETEX REQUIRES USING THE FIRE ALARM
CONNECTION IN THE POWER SUPPLY:
CLOSED
connection is provided to the fire alarm system when
not in-alarm and OPEN when in-alarm. See power supply
instructions for details.
REMOTE BY-PASS: (5 & 6)
Connect normally open (N.O.) contact.
When the contact is closed momentarily, this will allow the door
to open without the alarm sounding. The unit will automatically
re-arm in 15 seconds after the door is closed (three quick audible beeps).
BY-PASS RELAY: (7,8 & 9) DRY contact output.
The BY-PASS relay is energized when the unit is disarmed by
the KEY or REMOTE BY-PASS to indicate to a remote indicator
that the door is not armed.
ALARM RELAY: (10, 11 & 12) DRY contact output.
The ALARM relay is energized when the unit is sounding its
alarm to indicate to a remote indicator that an unauthorized
exit has been attempted.
OUTSIDE KEY CONTROL
If the OKC option is used, the outside key bypasses
and rearms the alarm.
STATUS INDICATOR (SLIDE SWITCH)
ON: Green LED blinks every three seconds
when the unit is disarmed.
Red LED blinks every three seconds
when the unit is armed.
OFF: No status indication
103185 Page 10