Detex AT-5200 User Manual

Es5200—entry sentry tailgate detection system, Unpacking and disassembly, Wiring

background image

200

K

Q5

D8

sck

1 2 3 4

ON

MAG LOCK

RELAY

ALARM

RELAY

DOOR

RELAY

A PASSAGE

COMPLETE

REMOTE

DISPLAY

BYPASS LED

A CARD LED

B CARD LED

A CARD BUTTON

B CARD BUTTON

CALIBRATE

RELAY

B PASSAGE

COMPLETE

RELAY

LED

B

12 VDC POWER

A

GND

GND

DOOR

BYPASS
GND

DOOR LED

CALIBRATE
BUTTON

3. BI-DIRECTION CARD ENABLE

1. DOOR PROP ENABLE

2. BEEP DISABLE

4. CARD STACKING DISABLE

N/O

N/C

COM

N/O

N/C

COM

N/C

N/O

COM

N/C

N/O

COM

N/C

N/O

COM

INPUTS

SENSITIVITY-FACTORY PRE-SET

DO NOT ADJUST!

1: UNPACKING AND DISASSEMBLY

(see detail drawing in Assembly section)



Remove the two assemblies from packaging.
Receiver side has Key Switch and Indicator.



Remove three(3) 5/64” Allen Screws at upper,
middle, and lower points on each assembly.



Remove the Upper Cover. Set Upper Cover
aside.

(NOTE - Unplug wiring from circuit board
when removing the Receiver-side Upper
Cover)



Remove the Lower Cover and set aside.



Remove the two 1/4” Hex Standoffs at the top
and bottom of each electronics package, then
slide package up and lift off of Mounting Plate.



Repeat for opposite assembly.

4: WIRING

Definitions:

A & B Sides - If standing between the two units and Facing the unit with the Key, Left is “A” and
Right is “B.” (see diagram at right for detail)

Door Prop function - Monitors Door input for a held open door. Goes into Alarm if door is not closed
within 10 seconds, unless another Valid User input is seen.

ACS - Access Control System

Output Relays:

(Output contact rating: 1 Amp)

Mag Lock Relay - Can be used to control an Electric Lock in response to a Valid User input. Form C
(held 5 sec)

Alarm Relay - Connect to remote equipment to monitor Alarm conditions. (Alarms Include:
Tailgater, Door Prop, Loiter, and Tamper conditions)
Changes state to indicate
Alarm. Form C (2.5 second minimum duration)

Door Relay - Connect to remote equipment to monitor Door Status. Form C
(Follows Door Input)

“A” & “B” Passage Complete - These relays change state upon valid
passage of a user from the A or B side. Used to monitor for Time and
Attendance by remote equipment. Form C (held 1 sec)

Inputs:

(all Inputs share 2 common GNDs on connector)

Valid “A” Card - N/O contact from ACS that momentarily closes to indicate a
Valid User approaching from the “A” side.*

Valid “B” Card - N/O contact from ACS that momentarily closes to indicate a
Valid User approaching from the “B” Side *

* Enable Free Passage by shorting input for Valid A or B Card.

Bypass - N/O contact that enables Bypass when closed. Resets alarm. Same
function as Key Switch.

Door - Closed Loop from Door when Door is closed. Optional, used for
Door Prop monitoring and enhanced TDS operation.

Power - 12-24 VDC@ 500 mA (1 Amp supply suggested)

REMOTE DISPLAY CONNECTOR:

Optional

.

Refer to ES5200-R1 or R2 Instructions

SETUP and TEST

Switches:

(as shown on drawing)

1) Door Prop Enable - Turns on the Door Prop function when

placed in the ON position.

2) Beep Disable - Turns Off the Valid Card beep when placed in the ON position.

3) Bi-Direction Card Enable - Allows an A card input to pass in either direction when placed in the ON position.

4) Card Stacking Disable - Requires a Valid User to pass, or time out, prior to accepting another card input.

Key Switch on Upper Cover - Use to Bypass the unit (held) or to Reset an alarm (momentary).

Pushbuttons:

(as shown on drawing)

To Calibrate

:

Install lower covers. Verify clear beam path. Apply Power. Press Calibrate Button.

Keep beam path clear until Calibrate LED is ON (up to 60 sec). That’s all it takes to set up!

NOTE: If Tamper is enabled alarm may sound if cover is removed.

A & B Card buttons - Press to simulate an A or B - Card input (respectively) for test and troubleshooting purposes.

LEDs:

Calibrate : On - Calibrated. Flashing - Beam interruption or Calibration required. Off - During Calibration.

Inputs : Respective LED will illuminate when a closure is seen on any Input (A Card, B Card, Bypass, Door)

Upper Cover : See “ES5200 ENTRY SENTRY - USER INSTRUCTION”

Sensitivity:

(as shown on drawing)

Clockwise: Increase Sensitivity - Reduce loiter time to 3 sec (min), improved step-over/crawl-under detection

Counter-Clockwise: Decrease Sensitivity - Increase loiter time up to 10 sec, reduce step-over/crawl-under detection.

SECURE

ACCESS

DOOR MNT. WALL MNT.




A B A B

CLEANING

-

Soft damp cloth, mild soap solution. Dry with soft cloth. Avoid using paper as this may

damage the optical surface. DSI recommends: Chemtronics® ES1668 www.chemtronics.com

RELAYS

SWITCHES

+ 12-24 VDC
- POWER

RECEIVER TRANSMITTER

+ 12-24 VDC
- POWER

(enlarged drawing on insert)

TAMPER JUMPER
(remove to enable)

DESIGNED SECURITY INC

1402 Hawthorne Street

Bastrop, Texas 78602

800 272 3555

Fax 512 321 9181

www.dsigo.com

Email: [email protected]

ES5200—ENTRY SENTRY

TAILGATE DETECTION SYSTEM

INS-5200 090907

SENSITIVITY ADJUSTMENT