By means of an NMT reset the encoder is re-initialized and is then once again in the pre-operational mode.
Reading the position
Request from the master:
COB ID
DLC Command
Object L
Object H Subindex Data 0
Data
1
Data
2
Data
3
600h+node ID
8
40h
04h
60h
0
0
0
0
0
Response (dcba) of the encoder to the request:
COB ID
DLC Command
Object L
Object H Subindex Data 0
Data
1
Data
2
Data
3
580h+node ID
8
43h
04h
60h
0
a
b
c
d
Configuring PDOs
The PDOs can be configured in accordance with the following table:
1800h
2800h
Summarized description
Sub2
Sub5
FEh
3ms
0
Cyclical transmission every 3 ms
FEh
5ms
2
Every 5ms the PDO is sent double if a change has occurred.
FEh
0ms
0
Transmit PDO switched off
FEh
0ms
xxx
Transmit PDO switched off
3
xxx
0
Transmit with each third sync telegram
3
xxx
2Bh
With each sync telegram but in total only 43 times (=2Bh).
Defining heartbeat time
In order to monitor communication capability, the heartbeat time must be defined in object 1017h with
"Producer heartbeat time". As soon as the value has been confirmed, the service begins transmission.
Example:
Every 100 ms, the encoder should transmit a heartbeat (100 = 64h):
COB ID
DLC Command
Object L
Object H
Subindex Data
0
Data 1
600h+node ID
8
2Bh
17h
10h
0h
64h
0h
Confirmation:
COB ID
DLC Command
Object L
Object H
Subindex Data
0
Data 1
580h+node ID
8
60h
17h
10h
0h
0
0
COB ID
Data/ Remote Byte 0
701h
d
7Fh
The heartbeat messages are made up of the COB ID and one byte. IN this byte, the NMT status is supplied.
0:
BootUp-Event
4:
Stopped
5:
Operational
127:
Pre-operational
i.e. the encoder is in the pre-operational modus (7Fh = 127).