Baumer G0-GB-GXP5W/S/H-GXU5W/S User Manual
Page 27

Manual_G0-GB-GXP5-GXU5_406_EN.docx
27/48
Baumer IVO GmbH & Co. KG
20.11.12
Villingen-Schwenningen, Germany
Object 1011
Restore parameters
The values in the RAM are overwritten by the default values (see object 1010h) by the object 1011h. In
addition, the content of the EEPROM is marked as invalid. This means that until the next data save
routine in the EEPROM, the default values are loaded in each case.
In order to prevent unintentional overwriting, the message "load" must be written in subindex 1.
COB ID
DLC Command
Object L
Object H Subindex
Data 0
Data
1
Data
2
Data
3
600h+node ID
8
23h
11h
10h
01
6Ch 'l'
6Fh
'o'
61h 'a' 64h 'd'
Object 1014
COB ID emergency message
Subindex
0
Data type
Unsigned 32
Access
Read write
Default
80h+node ID
EEPROM
Yes
Description
Defines COB ID of the emergency object
Values
80h + Node ID
Object 1016
Consumer heartbeat time
Subindex
0
Data type
Unsigned 8
Access
Read only
Default
1
EEPROM
No
Description
Biggest supported subindex
Values
1 = Biggest supported subindex
Subindex
1
Data type
Unsigned 32
Access
Read write
Default
10000h
EEPROM
Yes
Description
Consumer heartbeat time
Values
Bit 0..15 Consumer heartbeat time in ms
Bit 16..23 Node ID
Object 1017
Producer heartbeat time
Subindex
0
Data type
Unsigned 16
Access
Read write
Default
0h
EEPROM
Yes
Description
Defines repeat time of the heartbeat watchdog service
Values
0 = Disabled
1..65535 = Repeat time in ms