beautypg.com

Baumer G0-GB-GXP5W/S/H-GXU5W/S User Manual

Page 29

background image

Manual_G0-GB-GXP5-GXU5_406_EN.docx

29/48

Baumer IVO GmbH & Co. KG

20.11.12

Villingen-Schwenningen, Germany

Objekt 1029

Error Behavior (V1.04+)

Subindex

0

Data type

Unsigned 8

Access

ReadOnly

Default

1

EEPROM

No

Description

Biggest supported subindex

Values

1

Subindex

1

Data type

Unsigned 8

Access

ReadWrite

Default

1

EEPROM

Yes

Description

Behavior after communication error

Values

0h = change to Pre-Operational Mode
1h = no Mode-change
2h = change to Stop Mode
3h = reset node

Object 1800

PDO1 parameters

Subindex

0

Data type

Unsigned 32

Access

Read only

Default

5

EEPROM

No

Description

Biggest supported subindex

Values

5

Subindex

1

Data type

Unsigned 32

Access

Read write

Default

180h + Node ID

EEPROM

Yes

Description

COB ID of the PDO

Values

180h + Node ID

Subindex

2

Data type

Unsigned 8

Access

Read write

Default

FEh

EEPROM

Yes

Description

PDO type

Values

1..n..F0h = PDO has synchronous characteristics (the PDO is

transmitted to each nth SYNC telegram)

FEh =

PDO has asynchronous characteristics (PDOs are
transmitted cyclically depending on the event timer and
event trigger)

Subindex

5

Data type

Unsigned 16

Access

Read write

Default

203h

EEPROM

Yes

Description

Event timer for process data object

Values

0 =

Cyclical transmission switched off

1..n..65535 =Repeat time cyclical transmission equals n ms.