Baumer IVO GmbH & Co. KG

20.11.12

Villingen-Schwenningen, Germany

Object 2101

Node ID

Subindex

0

Data type

Unsigned 8

Access

Read write

Default

1

EEPROM

Yes

Description

Read or reset the node ID of the sensor.
 After setting, parameters must be stored in the EEPROM with the
object 1010h and then the sensor re-initialized

Values

1..127

Object 2110

Manufacturers Options

Subindex

0

Data type

Unsigned 32

Access

Read write

Default

8h

EEPROM

Yes

Description

To guarantee compatibility with older sensors some options could be
defined here.
This object is not supported by EDS File.
Modification should be done only by vendor.
Modification by customers very carefully according following table

Values

Bit1 = Code sequence (Objekt 6000h Bit0)

0

Not inverted

1

Inverted

Bit2 = scaling function (Objekt 6000h Bit2)

2

enabled

3

disabled

Bit3 = 0

BusOFF not removed

1

reinitate bus after BusOFF

Bit5 = 0 Heartbeat-Protokoll enabled

1 Nodeguarding-Protokoll enabled

Bit6 = 0 normal SYNC- response

1

fast SYNC- response (see Bit 7)

Bit7 = 0

alle PDO Modes enabled

1 only SYNC- Mode enabled
 lowest Jitter
(only together with set Bit 6)
Bit8 = PDO1 Delay 2ms

0

1800h-5h = 6200h

2 1800h-5h = 6200h + 2ms

Bit9 = Responce by write to object

Resolution/overall resolution

0 Offset reset
1 Offset not reset

(Version from V1.08)
Bit10 =Response by Reset Node (from V 1.09)

0 HW Reset

1 Init NMT state