Outputs / Other settings

Modem

43

Counters reset

44

50

55

•Type: type of alarm: up alarm (MAX); down alarm (MIN); up
alarm with latch (UP L): in this case the reset of the output
can only be manual; down alarm with latch (D.L.): in this
case the reset of the output can only be manual; down
alarm with disabling at power ON (D.DO). Choose the

desired alarm type by means of the

and

keys and

confirm it with

.

•Set on: ON-alarm set-point. Select the value of the vari-

able by means of the

and

keys and confirm it with

.

•Set off: OFF-alarm set-point. Select the value of the vari-

able by means of the

and

keys and confirm it with

.

•Out: Normally energized alarm (NE) or normally de-ener-
gized alarm (ND). Choose the desired function by means of

the

and

keys and confirm it with

.

•Delay: delay on alarm activation. Select the desired delay

value in seconds by means of the

and

keys and

confirm it with

.

S

S

S

S

S

Diagnostic

In a 3-phase unbalanced-load
system, this function controls the

S

presence of the neutral connection. If the connection to the
neutral is not detected, the instrument activates an alarm.

Select “DIAGNOSTIC” by means of the

and

keys,

then press

to confirm it. To reset your choice and go

back to the main menu, press

.

F

S