Adjus t menu – tekmar 423 Universal Reset Module User Manual
Page 9
9 of 36
© 2007
D 423 - 08/07
Item Field
Range
Access
Description
OFF, 40 to 150°F
(OFF, 4.5 to 65.5°C)
Default = OFF
Ad
MIX 1 MINIMUM
SECTION G
The minimum allowed Mix 1 target temperature.
Note: This item is only available when Bus 1 is set
to Mix 1.
80 to 220°F, OFF
(26.5 to 104.5°C, OFF)
Default = 140°F
(60.0°C)
Ad
MIX 1 MAXIMUM
SECTION G
The maximum allowed Mix 1 target temperature.
Note: This item is only available when Bus 1 is set
to Mix 1.
30 to 230 seconds
Default = 105
Ad
MIX 1 MOTOR
SECTION G
The time that the Mix 1 actuating motor requires to
operate from fully closed to fully open.
Note: This item is only available when Bus 1 is set
to Mix 1 and the Mixing Expansion Module is set to
Floating Action. Availability also depends on the type
of mixing module used.
1 HRF1
2 HRF2
3 Fancoil
4 Fin-tube Convector
5 Radiator
6 Baseboard
Default = 1
InS
Ad
MIX 2 TERMINAL
SECTION B
The type of heating terminal units that are being
used in Mix 2 zones.
Note: This item is only available when Bus 2 is set
to Mix 2.
40 to 100°F
(4.5 to 38.0°C)
Default = 70°F (21.0°C)
Ad
MIX 2 INDOOR
SECTION B
The design indoor air temperature used in the heat
loss calculation for Mix 2 zones. Typically set to
70°F (21.0°C).
Note: This item is only available when Bus 2 is set
to Mix 2.
70 to 220°F
(21.0 to 104.5°C)
Default = 120°F
(49.0°C)
InS
Ad
MIX 2 DESIGN
SECTION B
The supply water temperature required for the Mix 2
zones on the typical coldest day of the year.
Note: This item is only available when Bus 2 is set
to Mix 2.
OFF, 40 to 150°F
(OFF, 4.5 to 65.5°C)
Default = OFF
Ad
MIX 2 MINIMUM
SECTION G
The minimum allowed Mix 2 target temperature.
Note: This item is only available when Bus 2 is set
to Mix 2.
80 to 220°F, OFF
(26.5 to 104.5°C, OFF)
Default = 140°F
(60.0°C)
Ad
MIX 2 MAXIMUM
SECTION G
The maximum allowed Mix 2 target temperature.
Note: This item is only available when Bus 2 is set
to Mix 2.
Adjust Menu (2 of 7)
Continued on next page.