View menu display menus – tekmar 423 Universal Reset Module User Manual
Page 6
© 2007
D 423 - 08/07
6 of 36
View Menu (1 of 2)
Item Field
Range
Access
Description
-67 to 149°F
(-55.0 to 65.0°C)
InS
Ad
OUTDOOR
SECTION B
Current outdoor air temperature as measured by the
outdoor sensor.
-22 to 266°F
(-30.0 to 130.0°C)
InS
Ad
MIX 1 SUPPLY
SECTION B
Current Mix 1 supply water temperature as measured
by the Mix 1 supply sensor.
Note: This item is only available when Bus 1, 2 or
3 is set to Mix 1.
– – –, 35 to 230°F
(– – –, 1.5 to 110.0°C)
Ad
MIX 1 TARGET
SECTION B
The Mix 1 target is the temperature the control
is currently trying to maintain at the Mix 1 supply
sensor. “– – –” is displayed when no heat is required
for Mix 1 zones.
Note: This item is only available when Bus 1, 2 or
3 is set to Mix 1.
-22 to 266°F
(-30.0 to 130.0°C)
InS
Ad
MIX 2 SUPPLY
SECTION B
Current Mix 2 supply water temperature as measured
by the Mix 2 supply sensor.
Note: This item is only available when Bus 2 is set
to Mix 2.
– – –, 35 to 230°F
(– – –, 1.5 to 110.0°C)
Ad
MIX 2 TARGET
SECTION B
The Mix 2 target is the temperature the control
is currently trying to maintain at the Mix 2 supply
sensor. “– – –” is displayed when no heat is required
for Mix 2 zones.
Note: This item is only available when Bus 2 is set
to Mix 2.
-31 to 266°F
(-35.0 to 130.0°C)
InS
Ad
MIX 3 SUPPLY
SECTION B
Current Mix 3 supply water temperature as measured
by the Mix 3 supply sensor.
Note: This item is only available when Bus 3 is set
to Mix 3.
– – –, 35 to 230°F
(– – –, 1.5 to 110.0°C)
Ad
MIX 3 TARGET
SECTION B
The Mix 3 target is the temperature the control
is currently trying to maintain at the Mix 3 supply
sensor. “– – –” is displayed when no heat is required
for Mix 3 zones.
Note: This item is only available when Bus 3 is set
to Mix 3.
The View Menu items display the current operating
temperatures and status information of the system.
Continued on next page.
VIEW MENU
Display Menus