Adjust Menu (7 of 7)

ADJUS

T MENU

Item Field

Range

Access

Description

OFF, On

Default = OFF

Ad

SETPOINT (UnOccupied)

SECTION J

Selects whether or not a Setpoint Demand will be
responded to during the Sleep and Unoccupied
periods.

Note: This item is only available when Setpoint Mode
is set 1 through 4 and the Schedule Setting is set to
Member 1, 2, 3 or 4.

40 to 100°F, OFF

(4.5 to 38.0°C, OFF)

Default = 70°F (21.0°C)

InS

Ad

WWSD (Occupied)

SECTION B

The system’s warm weather shut down temperature
during the Wake and Occupied periods. The WWSD
applies to the space heating loads only. It does not
affect DHW or Setpoint heating loads.

40 to 100°F, OFF

(4.5 to 38.0°C, OFF)

Default = 60°F (15.5°C)

Ad

WWSD (UnOccupied)

SECTION B

The system’s warm weather shut down temperature
during the Sleep and Unoccupied period.
Note: This item is only available when the Schedule
Setting is set to Member 1, 2, 3 or 4.

After the last item, the control returns to the first item in the menu.