tekmar 423 Universal Reset Module User Manual
Page 27

27 of 36
© 2007
D 423 - 08/07
DHW
Pump
Primary
Pump
OFF
DHW Priority Override Time
Increasing Time
Decreasing Outdoor Air Temperature
DHW Priority Override
DHW Priority Override applies to DHW MODE 2 and 4. 
To prevent the building from cooling off too much or the 
possibility of a potential freeze up during DHW priority, the 
control limits the amount of time for DHW priority. As the 
outdoor air temperature becomes colder, the length of time 
that the control provides DHW priority is reduced. Once the 
allowed time for priority has elapsed, the control overrides 
the DHW priority and resumes space heating.
Conditional DHW Priority
If the boiler supply temperature is maintained at or above the 
required temperature during DHW generation, this indicates 
that the boiler has enough capacity for DHW and possibly 
heating as well. As long as the boiler supply temperature 
is maintained near the target, DHW and heating occurs 
simultaneously.
DHW Post Purge
After the DHW Demand is removed, the control performs 
a purge on the boiler. The control shuts off the boiler and 
continues to operate the DHW Pump and DHW Valve and 
the primary pump if applicable. This purges the residual heat 
from the boiler into the DHW tank. The control continues 
this purge for a maximum of four minutes or until the boiler 
supply water temperature drops 20°F (-6.5°C) below the 
boiler target temperature during the DHW operation. The 
control also stops the purge if the boiler supply temperature 
drops below the current boiler target temperature.
DHW Mixing Purge
After DHW operation, the boiler is extremely hot. At the same 
time, the heating zones may have cooled off considerably 
after being off for a period of time. When restarting the 
heating system after a DHW Demand with priority, the 
control shuts off the boiler and continues to operate the 
DHW Pump and DHW Valve while the primary pump is 
turned on. This allows some of the DHW return water to 
mix with the cool return water from the zones and temper 
the boiler return water.
DHW with Low Temperature Boilers
Section I
If DHW heating is to be incorporated into a low temperature 
system such as a radiant floor heating system, a mixing 
device is often installed to isolate the high DHW supply 
temperature from the lower system temperature. If a mixing 
device is not installed, high temperature water could be 
supplied to the low temperature system while trying to 
satisfy the DHW Demand. This may result in damage to 
the low temperature heating system.
The control is capable of providing DHW heating in such a 
system while minimizing the chance that the temperature 
in the heating system exceeds the design supply water 
temperature. In order to do this, the control must be set 
to DHW MODE 2 or DHW MODE 4 and Boil MIN must be 
set to OFF.
On a call for DHW, the control provides DHW priority by 
sending a message on the boiler temperature bus to the 
tN4 thermostats to shut off the heating zones for a period 
of time. The length of time is based on the outdoor air 
temperature as described in the DHW Priority Override 
section. However, if the DHW Demand is not satisfied within 
the allotted time, the boiler shuts off and the heat of the 
boiler is purged into the DHW tank. A DHW mixing purge 
occurs in order to reduce the boiler water temperature and 
once the boiler supply temperature is sufficiently reduced, 
the DHW Pump and DHW Valve contacts shut off. The 
heating system zones are allowed to turn on for a period 
of time to prevent the building from cooling off. After a 
period of heating, and if the DHW Demand is still present, 
the control shuts off the heating system and provides heat 
to the DHW tank once again.
