Adjus t menu – tekmar 423 Universal Reset Module User Manual

Page 10

background image

© 2007

D 423 - 08/07

10 of 36

Item Field

Range

Access

Description

30 to 230 seconds

Default = 105

Ad

MIX 2 MOTOR

SECTION G

The time that the Mix 2 actuating motor requires to
operate from fully closed to fully open.
Note: This item is only available when Bus 2 is set
to Mix 2, and the Mixing Expansion Module is set
to Floating Action. Availability also depends on the
type of mixing module used.

1 HRF1
2 HRF2
3 Fancoil
4 Fin-tube Convector
5 Radiator
6 Baseboard
Default = 1

InS

Ad

MIX 3 TERMINAL

SECTION B

The type of heating terminal units that are being
used in Mix 3 zones.
Note: This item is only available when Bus 3 is set
to Mix 3.

40 to 100°F

(4.5 to 38.0°C)

Default = 70°F (21.0°C)

Ad

MIX 3 INDOOR

SECTION B

The design indoor air temperature used in the heat
loss calculation for Mix 3 zones. Typically set to
70°F (21.0°C).
Note: This item is only available when Bus 3 is set
to Mix 3.

70 to 220°F

(21.0 to 104.5°C)

Default = 120°F

(49.0°C)

InS

Ad

MIX 3 DESIGN

SECTION B

The supply water temperature required for the Mix 3
zones on the typical coldest day of the year.
Note: This item is only available when Bus 3 is set
to Mix 3.

OFF, 40 to 150°F

(OFF, 4.5 to 65.5°C)

Default = OFF

Ad

MIX 3 MINIMUM

SECTION G

The minimum allowed Mix 3 target temperature.
Note: This item is only available when Bus 3 is set
to Mix 3.

80 to 220°F, OFF

(26.5 to 104.5°C, OFF)

Default = 140°F

(60.0°C)

Ad

MIX 3 MAXIMUM

SECTION G

The maximum allowed Mix 3 target temperature.
Note: This item is only available when Bus 3 is set
to Mix 3.

30 to 230 seconds

Default = 105

Ad

MIX 3 MOTOR

SECTION G

The time that the Mix 3 actuating motor requires to
operate from fully closed to fully open.
Note: This item is only available when Bus 3 is set
to Mix 3, and the Mixing Expansion Module is set
to Floating Action. Availability also depends on the
type of mixing module used.

Au (Auto)

OFF

Default = Au

InS

Ad

BOILER 1

SECTION C

Selects Whether Boiler 1 is operational or not.
Note: This item is only available when the Boil Sensor
Sup / Ret DIP Switch is set to Sup, and the tekmar
stager DIP switch is set to OFF.

Adjust Menu (3 of 7)

Continued on next page.

ADJUS

T MENU