Error Messages (4 of 5)
Error Message
Description
BOILER SENSOR OPEN CIRCUIT
Due to an open circuit, the control failed to read the boiler sensor. The control no longer controls 
the boiler. Instead, the control provides a boiler enable to the boiler’s aquastat or boiler control 
until the sensor is repaired. The control will not operate the boiler contact if the Boil Minimum 
setting is less than 100°F (38.0°C). Locate and repair the problem as described in the Data 
Brochure D 070. The error message self clears once the error condition is corrected
Note: If you deliberately remove the boiler sensor, set the Boiler Sensor Return / Supply DIP 
switch to Return. Power down for 10 seconds then restart the control.
OUTDOOR SENSOR SHORT CIRCUIT
Due to a short circuit, the control failed to read the outdoor sensor. As a result, the control 
assumes an outdoor temperature of 32°F (0.0°C) and continues operation. Locate and repair 
the problem as described in the Data Brochure D 070. The error message self clears once 
the error condition is corrected.
OUTDOOR SENSOR OPEN CIRCUIT
Due to an open circuit, the control failed to read the outdoor sensor. As a result, the control 
assumes an outdoor temperature of 32°F (0.0°C) and continues operation. Locate and repair 
the problem as described in the Data Brochure D 070. The error message self clears once 
the error condition is corrected.
DHW SHORT CIRCUIT
Due to a short circuit, the control failed to read the DHW sensor. As a result, the control no 
longer heats the DHW tank. Locate and repair the problem as described in the Data Brochure 
D 070. DHW tank heating will resume once the sensor problem is corrected. The error message 
self clears once the error condition is corrected.
DHW OPEN CIRCUIT
Due to an open circuit, the control failed to read the DHW sensor. As a result, the control no 
longer heats the DHW tank. Locate and repair the problem as described in the Data Brochure 
D 070. DHW tank heating will resume once the sensor problem is corrected. The error message 
self clears once the error condition is corrected.
DHW ERROR
A DHW Sensor and a DHW Demand have been applied at the same time. The DHW tank 
will not be heated until the DHW Demand signal is removed. The error message self clears 
once the error condition is corrected.
DEVICE SCHEDULE ERROR
The selected system schedule is no longer available. Either the system schedule master is 
no longer connected to the network or the system schedule number has been changed on 
the schedule master. The error message self clears once the error condition is corrected.
BOILER BUS AND RETURN SENSOR CONFLICT
There is a DIP switch settings conflict. The Boiler Sensor DIP Switch is set to Ret (Return) 
and there is a tN4 device on the Boiler bus. The error message clears once the tN4 device 
is removed from the Boiler bus or the DIP Switch is set to Sup (Supply).