Adjus t menu – tekmar 423 Universal Reset Module User Manual

Page 12

background image

© 2007

D 423 - 08/07

12 of 36

ADJUS

T MENU

Item Field

Range

Access

Description

0:00 to 3:00 min

Default = 0:10 min

Ad

BOILER FIRE DELAY

SECTION C

The time delay the control can expect between the
relay contact closes to fire the boiler and when the
burner actually fires.

Note: This item is only available when the Boiler
Sensor Sup / Ret DIP switch is set to Sup, and the
tekmar stager DIP switch is set to OFF.

10 to 230 seconds

Default = 30 seconds

Ad

BOILER MOTOR

SECTION C

The amount of time required for the modulating actuating
motor to fully open the gas valve or operate the fan
speed from a stopped position to full speed.

Note: This item is only available when the Boiler
Sensor Sup / Ret DIP switch is set to Sup, the Boiler
On-Off / Mod DIP switch is set to Mod and the tekmar
stager DIP switch is set to OFF.

0 to 50%

Default = 0%

Ad

BOILER MINIMUM MODULATION

SECTION C

The minimum percent modulation of the burner.

Note: This item is only available when the Boiler Sensor
Sup / Ret DIP switch is set to Sup, the Boiler On-Off /
Mod DIP switch is set to Mod, and the tekmar stager
DIP switch is set to OFF.

Au (Auto),

5 to 30 min

Default = Au

Ad

CYCLE LENGTH
The cycle length to which all tN4 devices will
synchronize.

OFF,
Mb1 (Member 1),
Mb2 (Member 2),
Mb3 (Member 3),
Mb4 (Member 4),
Default = OFF

InS

Ad

SCHEDULE
Selects which network setback schedule the control
will follow.

OFF,
1 (parallel, no priority)
2 (parallel, priority)
3 (pri-sec, no priority)
4 (pri-sec, priority)
Default = 1

InS

Ad

DHW MODE

SECTION H

Selects the DHW mode of operation. This determines
the operation of the primary pump in combination
with the DHW Pump / Valve and whether or not DHW
priority is required.

OFF, 70 to 190°F

(OFF, 21.0 to 87.5°C)

Default = 140°F

(60.0°C)

InS

Ad

DHW (Occupied)

SECTION H

The temperature of the DHW tank during the Wake
and Occupied periods.

Note: This item is only available when DHW Mode
is set 1 through 4, and the Off / DHW Sensor DIP
Switch is set to DHW Sensor.

Adjust Menu (5 of 7)

Continued on next page.