Adjus t menu – tekmar 423 Universal Reset Module User Manual

Page 11

background image

11 of 36

© 2007

D 423 - 08/07

Item Field

Range

Access

Description

Au (Auto)

OFF

Default = Au

InS

Ad

BOILER 2

SECTION C

Selects whether Boiler 2 is operational or not.

Note: This item is only available when the Boil Sensor
Sup / Ret DIP Switch is set to Sup, and the tekmar
stager DIP switch is set to OFF.

1 HRF1
2 HRF2
3 Fancoil
4 Fin-tube Convector
5 Radiator
6 Baseboard
Default = 4

InS

Ad

BOILER TERMINAL

SECTION B

The type of heating terminal units that are being
used in boiler zones.

Note: This item is only available when the Boiler
Sensor Sup / Ret DIP switch is set to Sup.

40 to 100°F

(4.5 to 38.0°C)

Default = 70°F

(21.0°C)

Ad

BOILER INDOOR

SECTION B

The design indoor air temperature used in the heat
loss calculation for the boiler zones. Typically set to
70°F (21.0°C).

Note: This item is only available when the Boiler
Sensor Sup / Ret DIP switch is set to Sup.

70 to 220°F

(21.0 to 104.5°C)

Default = 180°F

(82.0°C)

InS

Ad

BOILER DESIGN

SECTION B

The supply water temperature required for boiler
zones on the typical coldest day of the year.

Note: This item is only available when the Boiler
Sensor Sup / Ret DIP switch is set to Sup.

OFF, 80 to 180°F

(OFF, 26.5 to 82.0°C)

Default = 140°F

(60.0°C)

InS

Ad

BOILER MINIMUM

SECTION C

The minimum allowed boiler target temperature and
boiler return protection temperature. Check the boiler
manufacturer’s manual for recommend supply water
temperatures.

90 to 225°F, OFF

(32.0 to 107.0°C, OFF)

Default = 200°F

(93.5°C)

Ad

BOILER MAXIMUM

SECTION C

The maximum allowed boiler target temperature.

Note: This item is only available when the Boiler
Sensor Sup / Ret DIP switch is set to Sup and the
tekmar stager DIP switch is set to OFF.

Au (Auto), 2 to 42°F

(Au, 1 to 23.5°C)

Default = Au

Ad

BOILER DIFFERENTIAL

SECTION C

The temperature differential that the control is to use
to cycle the boiler On and Off.

Note: This item is only available when the Boiler
Sensor Sup / Ret DIP switch is set to Sup and the
tekmar stager DIP switch is set to OFF.

Au (Auto), 0.5 to

20.0 minutes

Default = Au

Ad

STAGE DELAY

SECTION C

The minimum time delay between the operation of
stages.

Note: This item is only available when the Boiler
Sensor Sup / Ret DIP switch is set to Sup and the
tekmar stager DIP switch is set to OFF.

Adjust Menu (4 of 7)

Continued on next page.

ADJUS

T MENU