beautypg.com

tekmar 423 Universal Reset Module User Manual

Page 20

background image

© 2007

D 423 - 08/07

20 of 36

Mix Characterized Heating Curve

Terminal Unit

Mix

Design

Outdoor

Design

Mix

Indoor

Decreasing Outdoor Temperatures

Increasing Mix T

e

mper

ature

Boiler Characterized Heating Curve

Terminal Unit

Boiler

Design

Boiler

Indoor

Outdoor

Design

Decreasing Outdoor Temperatures

Increasing W

a

ter T

e

mper

atures

Boiler Outdoor Reset

There is a water temperature and therefore a characterized
heating curve for each communication bus. When using
boiler temperature water to heat zones, the installer will be
required to set a boiler characterized heating curve.

Boiler Terminal Unit Defaults
When a terminal unit is selected for boiler zones, the
control loads default values for the boiler design, boiler
maximum supply, and boiler minimum supply temperatures.
The factory defaults can be changed to better match the
installed system. Locate the Boiler Terminal Unit setting
in the Adjust Menu.

Terminal Unit

BOIL DSGN

BOIL MAX

BOIL MIN

High Mass Radiant (1)

120°F (49°C)

140°F (60°C)

OFF

Low Mass Radiant (2)

140°F (60°C)

160°F (71°C)

OFF

Fancoil (3)

190°F (88°C)

210°F (99°C)

140°F (60°C)

Fin-Tube Convector (4) 180°F (82°C)

200°F (93°C)

140°F (60°C)

Radiator (5)

160°F (71°C)

180°F (82°C)

140°F (60°C)

Baseboard (6)

150°F (76°C)

170°F (77°C)

140°F (60°C)

Boiler Indoor Design
The boiler indoor design temperature is the indoor temperature
the heating designer chose while calculating the heat loss for
the boiler water heated zones. This temperature is typically
70°F (21.0°C). This setting establishes the beginning of
the boiler characterized heating curve.

• Locate the Boiler Indoor Design setting in the Adjust

Menu.

Boiler Design Temperature
The boiler design supply temperature is the boiler water
temperature required to heat the zones on the typical
coldest day of the year.

• Locate the Boiler Design setting in the Adjust Menu.

Mix 1, Mix 2 and Mix 3 Outdoor Reset

Each tN4 communication bus operates on a separate water
temperature. Therefore a separate characterized heating
curve is required for Mix 1, Mix 2 and Mix 3.

Mix 1, 2 and 3 Terminal Unit Defaults
When a terminal unit is selected for Mix 1, 2, or 3, the control
loads default values for the mix design, mix maximum supply,
and mix minimum supply temperatures. The factory defaults
can be changed to better match the installed system.

• Locate the Mix 1, Mix 2 and Mix 3 terminal unit settings

in the Adjust Menu.

Terminal Unit

MIX DSGN

MIX MAX

MIX MIN

High Mass Radiant (1)

120°F (49°C)

140°F (60°C)

OFF

Low Mass Radiant (2)

140°F (60°C)

160°F (71°C)

OFF

Fancoil (3)

190°F (88°C)

210°F (99°C)

100°F (38°C)

Fin-Tube Convector (4) 180°F (82°C)

200°F (93°C)

OFF

Radiator (5)

160°F (71°C)

180°F (82°C)

OFF

Baseboard (6)

150°F (76°C)

170°F (77°C)

OFF

Mix 1, Mix 2 and Mix 3 Indoor Design
The Mix 1, Mix 2 and Mix 3 indoor design temperature is
the indoor temperature the heating designer picked while
calculating the heat loss for the building for the Mix 1, Mix 2,
or Mix 3 water heated zones. This temperature is typically
70°F (21.0°C). This setting establishes the beginning of
the Mix 1, Mix 2, or Mix 3 characterized heating curve.

• Locate the Mix 1, Mix 2 and Mix 3 Indoor Design settings

in the Adjust Menu.

Mix 1, Mix 2, and Mix 3 Design Temperature
The Mix 1, Mix 2, and Mix 3 design supply temperature is
the mix supply water temperature required to heat the zones
when the outdoor temperature is as cold as the outdoor
design temperature.

• Locate the Mix 1, Mix 2 and Mix 3 Design settings in the

Adjust Menu.