Item Field

Range

Access

Description

boil, M1 (Mix 1), OFF

Default = boil

Ad

BUS 1

SECTION C

Select the water temperature for tN4 Bus 1.

boil, M1 (Mix 1),

M2 (Mix 2), OFF

Default = boil

Ad

BUS 2

SECTION C

Select the water temperature for tN4 Bus 2.

Note: M1 is only available if Bus 1 is set to M1
(Mix 1).

boil, M1 (Mix 1),

M3 (Mix 3), OFF

Default = boil

Ad

BUS 3

SECTION C

Select the water temperature for tN4 Bus 3.

Note: M1 is only available if Bus 1 is set to M1
(Mix 1).

-60 to 45°F

(-51.0 to 7.0°C)

Default = 10°F

(-12.0°C)

InS

Ad

OUTDOOR DESIGN

SECTION B

The design outdoor air temperature used in the heat
loss calculations for the heating system. Typically
set to the outdoor temperature of the coldest day
of the year.

1 HRF1
2 HRF2
3 Fancoil
4 Fin-tube Convector
5 Radiator
6 Baseboard
Default = 1

InS

Ad

MIX 1 TERMINAL

SECTION B

The type of heating terminal units that are being
used in Mix 1 zones.

Note: This item is only available when Bus 1 is set
to Mix 1.

40 to 100°F

(4.5 to 38.0°C)

Default = 70°F (21.0°C)

Ad

MIX 1 INDOOR

SECTION B

The design indoor air temperature used in the heat
loss calculation for Mix 1 zones. Typically set to
70°F (21.0°C).

Note: This item is only available when Bus 1 is set
to Mix 1.

70 to 220°F

(21.0 to 104.5°C)

Default = 120°F

(49.0°C)

InS

Ad

MIX 1 DESIGN

SECTION B

The supply water temperature required for the Mix 1
zones on the typical coldest day of the year.

Note: This item is only available when Bus 1 is set
to Mix 1.

Adjust Menu (1 of 7)

Continued on next page.

ADJUS

T MENU

The Adjust Menu items are the programmable settings
used to operate the mechanical equipment.