Setpoint Priority Override
Setpoint Priority Override applies to SETPOINT MODE 2 
and MODE 4. To prevent the building from cooling off 
too much or the possibility of a potential freeze up during 
setpoint priority, the control limits the amount of time for 
setpoint priority. As the outdoor air temperature becomes 
colder, the length of time the control provides setpoint 
priority is reduced. Once the allowed time for priority has 
elapsed, the control overrides the setpoint priority and 
resumes space heating.
Conditional Setpoint Priority
If the boiler supply temperature is maintained at or above 
the required temperature during setpoint generation, this 
indicates that the boiler has enough capacity for setpoint 
and possibly heating as well. As long as the boiler target 
temperature is maintained, setpoint and heating occur at 
the same time.
Pump Operation
Section K
Primary Pump
The primary pump is switched on in the following 
situations:
• 
• There is a Boiler Demand and that zone’s thermostat
has H1 Pump set to ON.
•
• There is a Mix 1, Mix 2 or Mix 3 Demand.
• 
• There is a DHW Demand and the control is set to DHW
Mode 3 or 4.
•
• The control is completing a DHW Purge.
• 
• There is a Setpoint Demand and the control is set to
Setpoint Mode 3 or Mode 4.
DHW Pump
The DHW Pump operates whenever there is a DHW Demand 
and the control is not in DHW Priority Override.
Pump Exercising
Section L
The system control will exercise all pumps, mixing valves and hydronic zones (zone valves and zone pumps) for 10 seconds 
every three days to prevent seizure.