Setup menu (2 of 7) – tekmar 553 Thermostat Installation User Manual

Page 28

background image

© 2014

553_D - 09/14

28 of 52

A Watts Water Technologies Company

Setting

Display

W PUMP
Select whether the primary or mix system pump on
a tekmarNet

®

system control should operate while

the first stage of heat W is operating.
Access Level: Installer

Range: OFF or ON

Conditions: Only available when a tekmarNet

®

system

control is connected and W TERM is set to HRF1 or
HRF2 or connected to a tN2 Wiring Center.

Default: ON

W THERMAL MOTOR
Select whether the first stage of heat W operates a
thermally actuated zone valve (wax actuator). When
set to ON, there is a 3 minute delay before operating
the pump and any heat sources.
Access Level: Installer

Range: OFF or ON

Conditions: Only available when a tekmarNet

®

system control is connected and W TERM is set to
HRF1 or HRF2 or connected to a tN2 Wiring Center.

Default: OFF

ACCESSORY RELAY
Select the equipment the accessory relay operates.
W2 = Second stage heat
HUM = Humidifier
DHUM = Dehumidifier
HRV = HRV for dehumidification
FAN = Intermittent fan

Access Level: Installer

Range: OFF, W2, HUM, DHUM,
HRV, FAN

Conditions: Always available.

Default: W2

W2 TERMINAL
Select the type of second stage W2 heating.
CONV = Baseboard convectors
COIL = Hydronic fan coil
FURN = Forced air furnace
OTHR = Non-hydronic heating that does not require
the fan to operate

Access Level: Installer

Range: CONV, COIL, FURN, OTHR

Conditions: ACC RELAY is set to W2.

Default: FURN (standalone)
COIL (tekmarNet

®

System Control)

W2 SOURCE
Select the water temperature of the W2 heating.
Access Level: Installer

Range: BOIL, TANK, MIX

Conditions: ACC RELAY is set to W2 and W2 TERMINAL
is set to CONV or COIL.

Default: BOIL

Setup Menu (2 of 7)