Monitor Menu (1 of 4)

Setting

Display

ROOM AVERAGE
Current room temperature. Displays the average if
there are multiple room sensors.

Access Level: Installer

Range: -58 to 212°F
(-50.0 to 100.0°C)

Conditions: Sensor 1 or 2 is set to ROOM.

Default: Not applicable.

FLOOR AVERAGE
Current floor temperature. Displays the average if
there are multiple floor sensors.

Access Level: Installer

Range: -58 to 212°F
(-50.0 to 100.0°C)

Conditions: Sensor 1 or 2 is set to FLOR.

Default: Not applicable.

AIR GROUP AVERAGE
Average room temperature of the thermostat and all
air group member thermostats.

Access Level: Installer

Range: -58 to 212°F
(-50.0 to 100.0°C)

Conditions: Setup menu setting Air Group Master
must be set to 1 through 16.

Default: Not applicable.

W SUPPLY
First stage heating supply water temperature.

Access Level: Installer

Range: -22 to 266°F
(-30.0 to 130.0°C)

Conditions: W TERM set to HRF1, HRF2, CONV
or COIL.

Default: Not applicable.

ROOM LOCAL
The built-in room sensor temperature measurement.

Access Level: Installer

Range: -58 to 212°F
(-50.0 to 100.0°C)

Conditions: Setup menu setting Room Sensor is
set to ON.

Default: Not applicable.

SENSOR 1
The temperature measurement from the sensor 1
input wiring terminals.

Access Level: Installer

Range: -58 to 212°F
(-50.0 to 100.0°C)

Conditions: Sensor 1 is set to ROOM, FLOR, COIL
or DUCT.

Default: Not applicable.