Setting

Display

SCHEDULE
Select if the thermostat should change the temperature
automatically using a programmable schedule.
OFF = Programmable schedule is not used.
Zone = Applies to this thermostat only.
Master 1, 2, 3, 4 = In charge of one of four available
network schedules.
Member 1, 2, 3, 4 = Follows selected network
schedule.

Access Level: Installer, User

Range: OFF, Zone, Master 1, 2, 3,
4, Member 1, 2, 3, 4

Conditions: In a tekmarNet

®

system, settings adjustable

in Installer access level only.

Default: OFF

EVENT PER DAY
Select the number of temperatures per day.
Access Level: Installer, User

Range: 2 or 4

Conditions: Schedule setting is set to Zone or
Master 1, 2, 3, 4.

Default: 2

24 HOUR / 7 DAY

Access Level: Installer, User

Range: 24 hour or 7 day

Conditions: Schedule setting is set to Zone or Master
1, 2, 3, 4.

Default: 24 hour

OPTIMUM START
Select whether or not to use optimum start. The
thermostat learns the heat up and cool down rates
of the room and starts heating or cooling in advance
of Event 1 or Event 3.
Access Level: Installer, User

Range: OFF or ON

Conditions: A schedule must be in use.

Default: ON

Schedule Menu (2 of 2)