Item Field

Range

Access

Description

40 to 122°F

(4.5 to 50.0°C)

Default = 85°F

(29.5°C)

ADV

FLOOR MAXIMUM

SECTION

F

Maximum floor temperature.

Note: This item is only available when Sensor 1 or
2 is set to Floor.

OFF, ROOM,

FLOR (Floor),

REM (Remote)

Default = OFF

INST

ADV

SENSOR 1

SECTION A

Select the type of sensor connected to auxiliary
sensor input 1.

OFF, ROOM,

FLOR (Floor),

OUT (Outdoor)

Default = OFF

INST

ADV

SENSOR 2

SECTION A

Select the type of sensor connected to auxiliary
sensor input 2.

OFF, ON

Default = ON

INST

ADV

ROOM SENSOR

SECTION A

Selects whether the built-in room sensor is functional.

SYNC, AUTO

2 to 12

Default = AUTO

ADV

HEAT CYCLES PER HOUR

SECTION

D

Select the number of heating cycles per hour. SYNC
results in 5 CPH. All tN4 thermostats that are connected
and have the SYNC setting selected synchronize their
cycle to the same starting time.
Note: This item is only available when the tN4 System
Control DIP switch is set to Off.

CTRL, HRF1, HRF2,

COIL, CONV, RAD,

BASE, OTHR ,FURN

Default =CTRL

INST

ADV

HEAT 1 TERMINAL

SECTION

E

Select the type of heating terminal for first stage
heat.
Note: If CTRL is selected, the terminal unit selected
on the tN4 System Control is used.

OFF, ON

Default = ON

INST

ADV

HEAT 1 PUMP

SECTION

F

Select whether the system, primary, or mixing pump
on a tN4 System Control must operate while the first
stage heat is operating.
Note: This item is only available when the H1 Terminal
item is set to CTRL, HRF1, HRF2, Fan Coil, Convector,
Radiator, or Baseboard.

OFF, ON

Default = OFF

INST

ADV

HEAT 1 DELAY

SECTION

F

Select whether the system, primary, or mixing pump
on a tN4 System Control is delayed to allow a first
stage heat thermal motor zone valve to open. Select
On for thermal motor, select Off for zone pump or
motorized zone valve.
Note: This item is only available when the H1 Terminal
item is set to CTRL, HRF1, HRF2, Fan Coil, Convector,
Radiator, or Baseboard.

Adjust Menu (2 of 4)

Continued on next page.

ADJUS

T MENU