Adjus t menu – tekmar 544 Thermostat Installation User Manual
Page 7

7 of 36
© 2008
D 544 - 07/08
Item Field
Range
Access
Description
40 to 122°F
(4.5 to 50.0°C)
Default = 85°F
(29.5°C)
ADV
FLOOR MAXIMUM
SECTION
F
Maximum floor temperature.
Note: This item is only available when Sensor 1 or
2 is set to Floor.
OFF, ROOM,
FLOR (Floor),
REM (Remote)
Default = OFF
INST
ADV
SENSOR 1
SECTION A
Select the type of sensor connected to auxiliary
sensor input 1.
OFF, ROOM,
FLOR (Floor),
OUT (Outdoor)
Default = OFF
INST
ADV
SENSOR 2
SECTION A
Select the type of sensor connected to auxiliary
sensor input 2.
OFF, ON
Default = ON
INST
ADV
ROOM SENSOR
SECTION A
Selects whether the built-in room sensor is functional.
SYNC, AUTO
2 to 12
Default = AUTO
ADV
HEAT CYCLES PER HOUR
SECTION
D
Select the number of heating cycles per hour. SYNC
results in 5 CPH. All tN4 thermostats that are connected
and have the SYNC setting selected synchronize their
cycle to the same starting time.
Note: This item is only available when the tN4 System
Control DIP switch is set to Off.
CTRL, HRF1, HRF2,
COIL, CONV, RAD,
BASE, OTHR ,FURN
Default =CTRL
INST
ADV
HEAT 1 TERMINAL
SECTION
E
Select the type of heating terminal for first stage
heat.
Note: If CTRL is selected, the terminal unit selected
on the tN4 System Control is used.
OFF, ON
Default = ON
INST
ADV
HEAT 1 PUMP
SECTION
F
Select whether the system, primary, or mixing pump
on a tN4 System Control must operate while the first
stage heat is operating.
Note: This item is only available when the H1 Terminal
item is set to CTRL, HRF1, HRF2, Fan Coil, Convector,
Radiator, or Baseboard.
OFF, ON
Default = OFF
INST
ADV
HEAT 1 DELAY
SECTION
F
Select whether the system, primary, or mixing pump
on a tN4 System Control is delayed to allow a first
stage heat thermal motor zone valve to open. Select
On for thermal motor, select Off for zone pump or
motorized zone valve.
Note: This item is only available when the H1 Terminal
item is set to CTRL, HRF1, HRF2, Fan Coil, Convector,
Radiator, or Baseboard.