Adjust Menu (4 of 4)

ADJUS

T MENU

Item Field

Range

Access

Description

AUTO, OFF,

10% to 90%, ON

Default = AUTO

LTD

USER

INST

ADV

FAN OPERATION

SECTION

H

The minimum percentage of time the ventilation fan
operates during each event.
Auto operates with heat or cool.
On operates continuously.
% sets a minimum On time for each cycle.

Wake

UnOccupied

Occupied

Sleep

0:00 to 2:00 min

(10 sec increments)

Default = 0:30

ADV

FAN DELAY

SECTION

H

Set the fan’s delay time after a heating zone calls for
heat. This allows the fan coil to heat up and prevents
the fan from blowing cold air.
Note: This item is only available when H1 Terminal is
set to Coil or Furnace and Fan Mode is set to 1 or 2.

0:00 to 3:00 min

(10 sec increments)

Default = 0:30

ADV

FAN PURGE SECTION

H

Set how long the fan operates after a call for heating or
cooling ends. This purges any heat or cold remaining
in the fan coil.
Note: This item is only available when H1 Terminal is
set to Coil or Furnace and Fan Mode is set to 1 or 2.

NONE, ZONE, CTRL

Default = CTRL

ADV

WARM WEATHER SHUT DOWN

SECTION O

Set the outdoor temperature at which warm weather
shutdown occurs. Select whether the thermostat
follows the tN4 System Control’s or the zone’s WWSD
for scheduled events.

40 to 100°F, OFF

(4.5 to 38.0°C, OFF)

Default = 72°F

(22.0°C)

INST

ADV

WWSD OCCUPIED AND WAKE

SECTION

O

Set the Warm Weather Shut Down (WWSD) temperature
during Occupied and Wake events.
Note: This item is only available when WWSD is set
to Zone.

40 to 100°F, OFF

(4.5 to 38.0°C, OFF)

Default = 60°F

(15.5°C)

INST

ADV

WWSD UNOCCUPIED AND SLEEP

SECTION

O

Set the Warm Weather Shut Down temperature during
Unoccupied and Sleep events.
Note: This item is only available when WWSD is set
to Zone.

HEAT, COOL,

H/C, OFF

Default = H/C

INST

ADV

OPTIMUM START / STOP

SECTION

K

Select whether to use Optimum Start / Stop for heating,
cooling, or both.
Note: This item is only available when a HeatCool
schedule is selected.

After the last item, the control returns to the first item in the menu.