Item Field

Range

Access

Description

Actual Setting

ADJUST

Lo, Med, Hi

Default = Med

INST

ADV

BOILER 1 MASS

SECTION C

The thermal mass characteristics of the boiler.
Note: This item is only available when
Boiler 1 is set to Au.

ADJUST

1

Boiler

min

OFF, 0:10 to

19:55 minutes
Default = 0:20

min

ADV

BOILER PUMP 1 PURGE

SECTION H

The time the boiler pump remains on once the
boiler is turned off.
Note: This item is only available when
Boiler 1 = Au and Mode = 2, 4 or 5.

Note: The previous 2 menu items will repeat for up to four boilers that are set to Au.

ADJUST

AUTO, 5 to 30

minutes

Default = Auto

ADV

CYCLE LENGTH

SECTION M

The cycle length to which all tN4 devices will
synchronize.
Note: This item is only available when a tN4
device is present.

ADJUST

OFF,

1 (parallel, no priority)

2 (parallel, priority)

3 (pri-sec, no priority)

4 (pri-sec, priority)

5 (parallel with last

boiler, priority)

6 (dedicated DHW)

Default = OFF

ADV

DHW MODE

SECTION E

This determines the operation of the primary
pump in combination with the DHW pump and
whether or not DHW priority is required.
Note: This item is only available when the Pump
Sequencing DIP is set to Off. DHW Mode 5 is
only available if Mode = 2.

ADJUST

OFF, ON

Default = OFF

ADV

DHW SENSOR

SECTION E

Selects if a DHW sensor is to be used for
DHW generation.
Note: This item is only available when the Pump
Sequencing DIP is to Off AND DHW Mode is
set to either 1, 2, 3 or 4.

ADJUST

Occ

OFF, 70 to

190°F (OFF,

21.0 to 87.5°C)

Default = 140°F

(60.0°C)

INST

ADV

DHW OCCUPIED

SECTION E

The temperature of the DHW tank during the
Wake and Occupied periods.
Note: This item is only available when the DHW
Mode is set to either 1, 2, 3, 4 or 6 AND the DHW
Sensor is set to On AND the Pump Sequencing
DIP is set to Off.

ADJUST

UnOcc

OFF, 70 to

190°F

(OFF, 21.0 to

87.5°C)

Default = 120°F

(49.0°C)

ADV

DHW UNOCCUPIED

SECTION E

The temperature of the DHW tank during the
Sleep and Unoccupied periods.
Note: This item is only available when the
DHW Mode is set to either 1, 2, 3, 4 or 6 AND
the DHW Sensor is set to On AND the Pump
Sequencing DIP is set to Off, AND the Setback
DIP = Setback.

Adjust Menu (4 of 6)

Continued on next page.