tekmar 274 Boiler Control User Manual
Page 17

17 of 44
© 2012 274_D - 11/12
Flow Proof Delay Setting in Adjust Menu
The control waits a period of time to receive a flow proof 
demand from the time the primary pump turns on. If the 
control does not receive a flow proof demand within that 
period of time, the primary pump turns off and the stand-by 
primary pump (if active) turns on. The control then waits 
that period of time again for the stand-by primary pump to 
prove flow. If flow is not proven, the stand-by pump turns 
off. The period of time is set through the Proof Demand 
‘Pump’ DLY item in the Adjust menu and it is adjustable 
between 10 seconds and 3 minutes. 
Flow Proof Demand Test
The control includes a flow proof demand test in order to 
determine if the flow/pressure device has failed. A flow 
proof failure is detected if a flow proof is present after the 
pumps have been shut off for more than four minutes. This 
can occur if the flow proof device sticks in the on position 
even when flow has stopped in the system. A proof demand 
error will latch when this condition exists. 
Primary Pump Rotation Setting in Adjust Menu
The control rotates the pumps based on the Rotate item 
in the Adjust menu. Frequency of Rotation is based on the 
running time of the pumps. Rotation is done when the lead 
pump is off. If the lead pump runs continuously, the rotation 
is delayed for up to 12 hours. If the pump runs continuously 
and rotation is required, the control shuts off the lead pump 
and 1 second later the stand-by pump is turned on. This 
eliminates overloading the pump electrical circuit. Upon 
turning on the stand-by pump the flow proof input is checked 
after the flow proof demand delay time.
Primary Pump Purge
After the last valid demand is removed, the primary pump 
is operated for an additional purging time of at least 20 
seconds. If the last demand came from a tN4 zone, the 
control sends out a purge message to override the zone 
open for the duration of the boiler purge. At the end of 
the purge, the zone override is removed so the zone is 
allowed to close and turn off the primary pump. If the last 
demand came from a non-tN4 zone, the purge period for 
the primary pump is adjustable between 10 seconds and 
19:55 minutes.
Boiler Pump Operation
The control can operate individual boiler pumps when set 
to Mode 2, 4 or 5. Refer to the Boiler Operation section for 
more information about the mode settings.
A pre-purge operates the respective boiler pump for a period 
of time before the boiler is ignited in order to purge potential 
residual heat out of the boiler.
The pre-purge time is determined from the boiler mass 
setting. As the boiler mass setting is increased, the boiler 
pump pre-purge time is also increased. The pre-purge time 
is fixed at 4 seconds whenever a DHW / Setpoint demand 
is provided in order to reduce boiler pick-up times.
The control includes a boiler pump post-purge feature that 
operates the respective boiler pump for a period of time 
after the boiler is turned off. This feature will purge heat out 
of the boiler and aid in reducing “kettling”. The amount of 
time for the boiler pump post purge is adjustable between 
10 seconds and 19:55 minutes. See the boiler pump purge 
setting in the adjust menu. 
The control will exercise the Combustion Air Damper, all 
pumps, and tN4 zones (zone valves and zone pumps) for 
10 seconds every three days of inactivity to prevent seizure. 
To enable exercising, switch the Exercise / Off DIP to the 
Exercise position.
Exercising
Section I
The control has a built-in time clock to allow the control to 
operate on a schedule. A battery-less backup allows the 
control to keep time for up to 4 hours without power. The 
time clock supports automatic adjustment for Daylight 
Saving Time (DST) once the day, month, and year are 
entered. Use the Time menu to set the correct time, day, 
month, and year.
Note: The Setback / Off DIP Switch must be set to Setback 
before the Time menu can be accessed.
Time Clock
Section J
Daylight Savings Time Modes
Mode
DST Start
DST End
1
1st Sunday in April
Last Sunday in October
2
2nd Sunday in March
1st Sunday in November
