Adjus t menu, Adjust menu (3 of 6) – tekmar 274 Boiler Control User Manual

Page 31

background image

31

of

44

©

2012 274_D

-

11/12

Item Field

Range

Access

Description

Actual Setting

ADJUST

Au (Auto), 2 to

42°F

(Au, 1 to

23.5°C)

Default = Au

ADV

BOILER DIFFERENTIAL

SECTION C

The temperature differential that the control is
to use to cycle the boiler On and Off (half above
and half below target).

ADJUST

LoHi or LoLo

Default = LoHi

ADV

BOILER STAGE MODE

SECTION C

Selects the firing sequence of the stages when
using multi-stage boilers.
Note: Only available in Mode 3.

ADJUST

DMPR

‘Damper’, ALRT

‘Alert’

Default =

DMPR

ADV

RELAY

SECTION D

Selects the operation of the relay to be either
combustion air or alert.

ADJUST

OFF, Flow

Proof (FP),

Combustion Air

(CA)

Default = OFF

ADV

PROOF DEMAND

SECTION D

Selects the operation of the Proof Demand
to be either off, flow proof, or combustion air
damper.
Note: C.A. only available if RELAY is set to
DMPR.

ADJUST

Primary

min

0:10 to 3:00

minutes

Default = 0:30

(pump)

ADV

PUMP PROOF DEMAND DELAY

SECTION D

The time allowed for the control to receive a
proof demand once the primary pump turns on.
Note: Only available when PROOF DEMAND
is set to F P.

ADJUST

min

0:10 to 3:00

minutes

Default = 1:00

(damper)

ADV

CA PROOF DEMAND DELAY

SECTION D

The time allowed for the control to receive a proof
demand once the C.A. contact turns on.
Note: Only available if RELAY is set to DMPR AND
Proof Demand is set to C A.

ADJUST

min

0:00 to 3:00

minutes

Default = 1:00

ADV

DAMPER DELAY

SECTION D

The time delay for the boiler to operate once
the combustion air damper relay closes.
Note: Only available if RELAY is set to DMPR AND
Proof Demand is set to OFF or FP.

ADJUST

Au (Auto),

0:30 to 40:00

minutes

Default = Au

ADV

STAGE DELAY

SECTION C

The minimum delay between the operation of stages.
Note: This item is only available when at least
two boilers are set to Au.

ADJUST

1

min

0:00 to 3:00

minutes

Default = 0:10

ADV

BOILER 1 FIRE DELAY

SECTION C

Delay from turn-on of ignition until the burner
fires.
Note: This item is only available when
Boiler 1 is set to Au.

Adjust Menu (3 of 6)

Continued on next page.

ADJUS