beautypg.com

Terminals 17 - 26, Terminals 7 – 22 – tekmar 274 Boiler Control User Manual

Page 22

background image

©

2012 274_D

-

11/12

22

of

44

Outdoor Sensor (tekmar 070)
Connect the two wires from the Outdoor Sensor 070
to the Com and Out (2 and 3) terminals. The outdoor
sensor is used by the control to measure the outdoor air
temperature.
Note: If an Outdoor Sensor 070 is connected to a
tekmarNet

®

4 thermostat in the system, it is not required

to be connected to the control.
Boiler Supply Sensor (tekmar 082)
Connect the two wires from the Boiler Supply Sensor 082
to the Com and Boil (5 and 4) terminals. The Boiler Supply
Sensor is used by the control to measure the boiler supply
water temperature.
DHW or Boiler Return Sensor (tekmar 082)
Connect the two wires from the DHW Sensor 082 to the
Com and BRet / DHW (5 and 6) terminals. The DHW
Sensor is used by the control to measure the DHW water
temperature or the DHW Exchange Supply Temperature.
OR
Connect the two wires from the Boiler Return Sensor 082
to the Com and BRet / DHW (5 and 6) terminals. The Boiler
Return Sensor is used by the control to measure the boiler
return temperature.

+

-

Out

Com

3

2

Outdoor

Sensor

070

DHW Sensor 082

OR

Boiler Return Sensor 082

DHW

BRet/

Com

6

5

Sup

Com

Boil

5

4

Boiler Supply Sensor 082

Powered Output Connections

Terminals 17 - 26

Primary Pump P1
The Prim P1 output on terminal (18) is a powered output.
When the relay in the control closes, 115 V (ac) is provided
to the Prim P1 terminal (18) from the Power L terminal (19).
To operate the primary pump P1, connect one side of the
primary pump circuit to terminal (18) and the second side
of the pump circuit to the neutral (Power N) side of the 115
V (ac) power supply.

Primary Pump P2
The DHW / P2 output on terminal (17) is a powered output.
When the relay in the control closes, 115 V (ac) is provided
to the DHW / P2 terminal (17) from the Power L terminal
(19). To operate the primary pump P2, connect one side
of the primary pump circuit to terminal (17) and the second
side of the pump circuit to the neutral (Power N) side of the
115 V (ac) power supply.

N

L

Pump

Pump
L & N

18 19

20

Prim Power

P1

L

N

Primary

Pump

N

L

Pump

Pump
L & N

17

18 19

20

DHWPrim Power

P2

P1

L

N

Backup

Primary

Pump

OR

DHW

Pump

Non-Powered Output Connections

Terminals 7 – 22

Wiring the T-T
(RELAY TYPE = Boiler

)

Terminals 7-8, 9-10, 11-12 and 13-14 are dry contacts. No
power is available from these terminals. These contacts
can be used to either make or break power to a boiler or
boiler pump. The boiler must be wired to power as per the
manufacturers’ directions.
These terminals are typically connected to the boiler’s
control circuit (commonly labeled as T-T). Connect these
terminals directly to the boiler T-T connections.

4

3

2

1

Relay

Relay

Relay

Relay

14

13

12

11

10

9

8

7