beautypg.com

tekmar 260 Boiler Control User Manual

Page 8

background image

Copyright © D 260 -

03/09

8 of 20

FIRE DELAY (FIRE DELAY)

The Fire Delay is the delay time that occurs between the time that the 260 closes the

Boiler contact and the burner fires. This delay is

usually the result of burner pre-purge, or other forms of time delay built into the burner’s safety circuits.

BOILER DIFFERENTIAL (BOIL DIFF)

An on / off heat source such as a boiler, must be operated with a differential in order to prevent short cycling. With the 260, either a
fixed or an auto differential may be selected.

Fixed Differential

The boiler differential is divided around the BOIL TARGET temperature.
The contact will close when the supply water temperature is 1/2 of
the differential setting below the BOIL TARGET temperature, and will
open when the supply water temperature is 1/2 of the differential setting
above the BOIL TARGET temperature.

Auto Differential (Ad)

If the Auto Differential is selected, the 260 automatically determines
the best differential as the load changes. This setting is recommended
as it reduces potential short cycling during light loads.

WARM WEATHER SHUT DOWN (WWSD) OCC & UNOCC

When the outdoor air temperature rises above the WWSD setting, the 260 turns on the WWSD segment in the display. When the
control is in Warm Weather Shut Down, the

Boiler Demand pointer is displayed, if there is a demand. However, the control does not

operate the heating system to satisfy this demand. The control does respond to a DHW demand and operates as described in
section C.

Section C: Domestic Hot Water (DHW)

Section C1

General Domestic

Hot Water (DHW)

Operation

Section C2

DHW Priority

Section C3

DHW with Low

Temperature

Boiler

Section C1: General Domestic Hot Water (DHW) Operation

DHW DEMAND

A DHW demand is required in order for the 260 to provide heat to the DHW system. The
260 registers a DHW demand when a voltage between 24 and 240 V (ac) is applied
across the

DHW Demand terminals (3 and 4). A DHW aquastat or setpoint control is used

as a switch in the DHW demand circuit. Once the 260 detects a DHW demand, the

DHW

Demand pointer turns on in the LCD and the control operates as described below.

DHW DEVICE

Once the 260 receives a DHW demand, the sequence of operation depends on the type of
DHW device selected. The DHW device is selected using the

DHW Valve / DHW Pump

DIP switch.

Supply W

ater

T

emperature

Time

Differential = 10

°F (5°C)

165

°F(74°C)

B

o

ile

r

o

ff

B

o

ile

r

o

n

155

°F (68°C)

160

°F (71°C)

B

o

ile

r

o

ff

B

o

ile

r

o

n

3

4

DHW

Demand

24 to 240 V (ac)

Aquastat

Off

On

Time

Heating Load

Differential