tekmar 260 Boiler Control User Manual
Page 12

Copyright © D 260 -
03/09
12 of 20
DHW Pump / Valve Contact
The
DHW Pmp / Vlv terminals (9 and 10) are an isolated output in the 260. There is no
power available on these terminals from the control. These terminals are to be used
as a switch to either make or break power to the DHW pump or DHW valve. Since this
is an isolated contact, it may switch a voltage between 24 V (ac) and 240 V (ac).
Boiler Contact
The
Boiler terminals (11 and 12) are an isolated output in the 260. There is no power
available on these terminals from the control. These terminals are to be used as a
switch to either make or break the boiler circuit. When the 260 requires the boiler to
fire, it closes the contact between terminals 11 and 12.
Sensor and Unpowered Input Connections
Do not apply power to these terminals as this will damage the
control.
Outdoor Sensor
Connect the two wires from the Outdoor Sensor 070 to the
Com
and
Out terminals (14 and 16). The outdoor sensor is used by the
260 to measure the outdoor air temperature.
Boiler Sensor
Connect the two wires from the Boiler Sensor 0
82 to the Com and
Boil terminals (14 and 15). The boiler sensor is used by the 260 to
measure the supply (outlet) water temperature from the boiler.
Indoor Sensor
If an indoor sensor is used, connect the two wires from the sensor
to the
Com and Indr terminals (17 and 18). The indoor sensor is
used by the 260 to measure the room air temperature.
Unoccupied Switch
If an external timer (tekmar Timer 03
2) or switch is used, connect the two wires from
the external switch to the
UnO Sw and Com terminals (13 and 14). When these two
terminals are shorted together, the control registers an unoccupied signal.
STEP FIVE
TESTING THE WIRING
Each terminal block
must be unplugged from its header on the control before power is applied for testing. To remove a terminal
block, pull it straight down from the control.
The following tests are to be performed using standard testing practices and procedures, and should only be carried out by properly
trained and experienced persons.
A good quality electrical test meter, capable of reading from at least 0 - 300 V (ac) and at least 0 - 2,000,000 Ohms, is essential to
properly test the wiring and sensors.
9
10
DHW
Pmp/Vlv
24 to 240 V (ac)
M
or
11 12
T
T
T
T
Boiler
14
15
16
Com
Boil
Out
17 18
Com Indr
Boiler
sensor
14 15
Com Boil
13 14
Timer Switch
UnO
Sw
Com