View menu (1 of 1), Display description range – tekmar 260 Boiler Control User Manual

Page 15

background image

Copyright © D 260 -

03/09

15 of 20

Press and release the

Item button to advance to the ROOM UNOCC adjustment. Use the or button to

set the desired temperature. The ROOM UNOCC setting is set to the desired room air temperature during
the unoccupied (Night) mode.

Note: To increase or decrease space temperature during the unoccupied (Night) mode, only adjust the

ROOM UNOCC setting.

Press and release the

Item button to advance to the OUTDR DSGN adjustment. Use the or button to

set the outdoor design temperature. The OUTDR DSGN setting is set to the typical coldest temperature of
the year.

Press and release the

Item button to advance to the Terminal Unit adjustment. Use the or button to select

the desired terminal unit. The terminal unit number corresponds to the type of terminal that is being used.
The table below lists the terminal units and their default values.

Press and release the

Item button to advance to the units adjustment. Use the or button to set the scale

to

°F or °C.

To exit the ADJUST menu, press and release the

Item button to advance to the ESC item. Then either press

the or button, or leave the buttons alone for 20 seconds.

View Menu (1 of 1)

Current outdoor air temperature as measured by the outdoor
sensor. This is also the default display for the control.

-67 to 149

°F

(-55 to 65

°C)

Current room air temperature as measured by the indoor sensor.
(Indoor sensor is present)

23 to 113

°F

(-5 to 45

°C)

Current boiler supply water temperature as measured by the
boiler sensor.

14 to 266F
(-10 to 130

°C)

Target boiler supply is the temperature the control is currently
trying to maintain at the boiler sensor.

---, 14 to 266

°F

(---, -10 to 130

°C)

B1
B3

C1
C2

SectionInstaller

Display

Description

Range

B1

B3

ROOM

°

F

OCC

UN

ADJUST

°

F

ADJUST

Advanced

ADJUST

ADJUST

DSGN

OUTDR

°

F

Terminal Unit

ADJUST

VIEW

OUTDR

°F

OCC

VIEW

ROOM

°

F

OCC

VIEW

BOIL

°

F

OCC

VIEW

TARGET

BOIL

°

F

OCC

150

°F (66°C)

170

°F (77°C)

140

°F (60°C)

BOIL DSGN
BOIL MAX
BOIL MIN

Terminal Unit

190

°F (88°C)

210

°F (99°C)

140

°F(60°C)

High Mass Radiant

(1)

120

°F (49°C)

140

°F (60°C)

OFF

Low Mass Radiant

(2)

Fancoil

(3)

140

°F (60°C)

160

°F (71°C)

OFF

Fin-tube Convector

(4)

180

°F (82°C)

200

°F (93°C)

140

°F (60°C)

Radiator

(5)

160

°F (71°C)

180

°F (82°C)

140

°F (60°C)

Baseboard

(6)