Adjust Menu (1 of 2)

The desired room air temperature during an
occupied (Day) period.

35 to 100

°F

(2 to 38

°C)

The desired room air temperature during an
unoccupied (Night) period.

35 to 100

°F

(2 to 38

°C)

The design outdoor air temperature used in the
heat loss calculation for the heating system.

-60 to 32

°F

(-51 to 0

°C)

The design indoor air temperature used in the heat
loss calculation for the heating system.

35 to 100

°F

(2 to 38

°C)

B3

The design supply water temperature used in the
heat loss calculation for the heating system.

70 to 220

°F

(21 to 104

°C)

B3

The maximum boiler target supply water
temperature.

120 to 225

°F

(49 to 107

°C)

B3

The type of terminal units that are being used in the
heating system.

B2

The minimum temperature allowed for the boiler
target temperature.

OFF, 80 to 180

°F

(OFF, 27 to 82

°C)

B3

The system’s warm weather shut down during the
occupied (Day) period.

35 to 100

°F, OFF

(2 to 38

°C, OFF)

B3

The time delay the control can expect between the
time the boiler contact closes, and the burner fires.

0:00 to 3:00 min
(1 sec. increments)

B3

The differential that the control is to use when it is
operating the boiler.

Ad, 2 to 42

°F

(Ad, -17 to 6

°C)

B3

B2

B2

B2

1 (High Mass Radi-
ant), 2 (Low Mass
Radiant), 3 (Fancoil),
4 (Fin-tube Convec-
tor), 5 (Radiator),
6 (Baseboard)

Section

Advanced

Installer

Display

Description

Range

Actual

Setting

ADJUST

DIFF

BOIL

ADJUST

WWSD

°

F

OCC

ROOM

°

F

OCC

ADJUST

ROOM

°

F

OCC

UN

ADJUST

ADJUST

DSGN

OUTDR

°

F

ADJUST

INDR

BOIL

°

F

ADJUST

BOIL

°

F

MAX

ADJUST

BOIL

°

F

MIN

Fire Delay

ADJUST

min

Terminal Unit

ADJUST

ADJUST

DSGN

BOIL

°

F