Adjust menu (1 of 2), Display description range actual setting – tekmar 260 Boiler Control User Manual
Page 16

Copyright © D 260 -
03/09
16 of 20
Adjust Menu (1 of 2)
The desired room air temperature during an
occupied (Day) period.
35 to 100
°F
(2 to 38
°C)
The desired room air temperature during an
unoccupied (Night) period.
35 to 100
°F
(2 to 38
°C)
The design outdoor air temperature used in the
heat loss calculation for the heating system.
-60 to 32
°F
(-51 to 0
°C)
The design indoor air temperature used in the heat
loss calculation for the heating system.
35 to 100
°F
(2 to 38
°C)
B3
The design supply water temperature used in the
heat loss calculation for the heating system.
70 to 220
°F
(21 to 104
°C)
B3
The maximum boiler target supply water
temperature.
120 to 225
°F
(49 to 107
°C)
B3
The type of terminal units that are being used in the
heating system.
B2
The minimum temperature allowed for the boiler
target temperature.
OFF, 80 to 180
°F
(OFF, 27 to 82
°C)
B3
The system’s warm weather shut down during the
occupied (Day) period.
35 to 100
°F, OFF
(2 to 38
°C, OFF)
B3
The time delay the control can expect between the
time the boiler contact closes, and the burner fires.
0:00 to 3:00 min
(1 sec. increments)
B3
The differential that the control is to use when it is
operating the boiler.
Ad, 2 to 42
°F
(Ad, -17 to 6
°C)
B3
B2
B2
B2
1 (High Mass Radi-
ant), 2 (Low Mass
Radiant), 3 (Fancoil),
4 (Fin-tube Convec-
tor), 5 (Radiator),
6 (Baseboard)
Section
Advanced
Installer
Display
Description
Range
Actual
Setting
ADJUST
DIFF
BOIL
ADJUST
WWSD
°
F
OCC
ROOM
°
F
OCC
ADJUST
ROOM
°
F
OCC
UN
ADJUST
ADJUST
DSGN
OUTDR
°
F
ADJUST
INDR
BOIL
°
F
ADJUST
BOIL
°
F
MAX
ADJUST
BOIL
°
F
MIN
Fire Delay
ADJUST
min
Terminal Unit
ADJUST
ADJUST
DSGN
BOIL
°
F